Datasheet

Input
Voltage Range 55-150 VAC ± 5% or 110-300 VAC ± 5%
Frequency Range
40Hz ~ 70Hz
Power Factor
0.99 @ Nominal Voltage (100% Load)
Output
Output Voltage
110/115/120/127 VAC or 208/220/230/240VAC
Voltage Regulation
± 1%
Frequency range
(Synchronized Range)
47Hz ~ 53Hz or 57Hz ~ 63Hz
Frequency Range
(Batt. Mode)
50Hz ± 0.2Hz or 60Hz ± 0.2Hz
Current Crest Ratio
5:1 (max.)
Harmonic Distortion
2% THD (Linear Load) ; 8% THD (Non-linear Load)
Transfer
Time
Bypass to Inverter
Zero
Inverter to Bypass
4ms (typical)
Waveform (Batt. Mode)
Pure Sinewave
Efficiency
AC Line Mode
88%
Battery Mode
85%
Battery
Long-Run
Model
Battery Type /
Numbers
Depending on the capacity of external batteries
Charging Current
(max.)
4.0 A or 8.0 A
Default:4.0 A ± 10%, Max.:6.0A ± 10%
Float Charging Voltage
54,7 VDC ± 1% 82,1 VDC ± 1%
Indicators
LCD Display
Load Level, Battery level, AC Mode, Battery Mode, Bypass Mode and Fault Indicator
Alarm
Battery Mode
Sounding every 4 seconds
Low Battery
Sounding every second
Overload
Sounding twice every second
Fault
Continously sounding
AC Input & Output Connectors
AC Input Connector
1 x IEC 320 C20 1 x IEC 320 C20
AC Output Connector
8 x IEC 320 C13 1 x IEC 320 C19 / 6 x IEC 320 C13
Standards
IEC 62040-1 (Safety)
YES
IEC 62040-2 (EMC)
YES
CE
YES
Physical dimensions
Long-Run
Model
Dimension (mm)
480 (D) x 438 (W) x 88 (H) 600 (D) x 438 (W) x 88 (H)
Net Weight (kgs)
11,3 13,8
Environment
Humidity
20-90% RH @ 0-40°C (non-condensing)
Noise Level
Less tahn 50dBa @ 1 Meter
Management
Smart RS-232 / USB
Supports Windows 2000/2003/XP/Vista/2008/7/8, Linux, Unix, and MAC
Optional SNMP
Power management from SNMP manager and web browser
*Product specifications are subject to change without further notice.