FIELD SERVICE GUIDE
Problemsmostfrequentlyencounteredwithrefrigerated
dryersarewaterdownstreamofthedryerandexcessive
pressuredrop.Mostcausescanbeidentiedandremedied
byfollowingthisguide.
Closedrefrigerationsystemsarepotentially
dangerous.Workontherefrigerationsystemmustbedone
onlybyacompetentlicensedrefrigerationmechanic.Donot
releaseuorocarbonrefrigerantstotheatmosphere.Donot
dischargeliquidrefrigerantsintooordrains.Refrigerant
vaporsmayaccumulateinlowplaces.Inhalationofhigh
concentrationsmaybefatal.Allrefrigerantsmustbe
recoveredperEPArequirements.
Donotsmokewhenarefrigerationleakissuspected.Burning
materialsmaydecomposerefrigerants,formingatoxicgasor
acidsthatmaycauseseriousinjuryandpropertydamage.
Beforedismantlinganypartofthedryerorcompressed
airsystem,completelyventtheinternalpressuretothe
atmosphere.
PROBLEM SYMPTOM POSSIBLE CAUSE REMEDY
Water Downstream of
Dryer
Refrigerantcompressornot
running.
Lossofpowertodryer Checkpowersupply,fusesand/orbreakers.Check
forlooseconnections.
Dryerturnedoff. CheckOn/Offswitchposition.
Dryeroverloaded. Conrmthatinletow,inlettemperatureandinlet
pressurearewithinacceptablerangeofdryer.
Condenser clogged with debris. Check/cleanambientairlterandcondenser.
Fan motor inoperative Checkfanmotoroperation.Replaceifnecessary.
Ambienttemperaturetoohigh. Verifyambienttemperaturethroughoutday.
Highpressureswitchactivated
(models 200 to 500 only)
Pressmanualresetbuttontoswitchtoresetbutton.
Compressor overheated. Turndryeroff.Contactlocaldistributor.
Compressordefective. Turndryeroff.Contactlocaldistributor.
Nocondensatedischargingfrom
dryer.
Drainstrainerclogged. Clean drain strainer.
Drainvalveinoperative. Check/rebuilddrainvalve.
DraintimerorDSMinoperative. ConrmthereispowertothetimerorDSM.
ReplacetimerorDSM,ifnecessary.
Drainsolenoidinoperative. Conrmthereispowertothecoil.Replacecoil,if
necessary.
Condensatedischargingfromdryer. Incorrectdraintimersetting. Adjustdraintimer-increaseopentimeand/or
decrease closed time.
Liquidwaterenteringdryer. Aftercoolerdrainvalvemalfunction. Check,repairaftercoolerdrainvalve.
Excessive Pressure
Drop Across Dryer
Frozencondensateinevaporator. Incorrecthotgasbypassvalve
setting.
Contact local distributor.
Inletairpressurelow. Upstreamrestrictioninairsystem. Checkallupstreamairsystemcomponents(valves,
regulators,etc.)
Dryerundersized. Excessivecompressedairow. Resizedryer.
Dew Point Indicator
Out of Green Zone
Dryeroverloaded. Conrmthatinletow,inlettemperatureandinlet
pressurearewithinacceptablerangeofdryer.
Condenser clogged with debris. Check/cleanambientairlterandcondenser.
Loosesensorconnection. ConrmgaugeorDSMsensoristightlyconnected
to dryer tubing.
Defectivegauge,DSMorDSM
sensor.
Replacegauge,DSMorDSMsensor.