Use and Care Manual
4
INSTRUMENTATION
ON/OFF Switch
ThedryerisequippedwithanON/OFFswitchonthefront
panel.Alightsignalswhenthedryerison.
Dew Point Indicator
(75 through 150 scfm models)
Alldryersareequippedwithadewpointindicatorwhich
indicatesdryerconditionsasfollows:
Itisnormalforthedewpointindicatortobeintheredzone
whenthedryerisrstturnedonandthenmovetothe
greenzonewhenthedryerreachesitsnormaloperating
temperature.Ifthisindicatorisintheredzoneduring
normaloperation,turnthedryerofftoavoidcompressor
damage.RefertotheFieldServiceGuideforadditional
information,orcallyourlocaldistributor.
Dryer System Monitor (DSM)
(200 through 5000 scfm models)
TheDryerSystemMonitor(DSM)hasLEDtypedewpoint
temperature indicators and electronic drain valve timing
controls.Whenthedryerisrunningnormally,thegreenLEDs
willilluminate.IftheredLEDisilluminated,thereisaneed
forthedryer'soperatingconditiontobechecked.
NOTE:Whenthedryeristurnedon,allLEDswillbe
illuminated.Allow15minutesfortheredandyellowLEDsto
beextinguished.
Theautomaticdrainvalvecontrolsallowtheperiodofdrain
openingtobesetfrom0.5secondsto9secondsanddrain
valveclosedtimetobesetfrom0.5minutesto9minutes.
Whenthe"PUHTOTEST"buttonispushed,thedrainvalve
opensandremainsopenfortheadjusted"open"time.
Automatic Drain Valve
Allmodelsareequippedwithanelectronicdrainvalvethat
automaticallydischargescondensatefromthedryer.Drain
valve operation is controlled by a drain valve timer. The drain
openingcanbesetfrom0.5secondsto9seconds.Thedrain
cyclecanbesetfrom0.5minutesto9minutes.
Models75through150havethetimermounteddirectlyon
thedrainvalve.Formodels200through500,drainvalve
adjustmentsaremadeontheDryerSystemMonitor(DSM).
Electronic Drain Valve Adjustment
Tominimizeairlosses,thedrainvalvecontroltimeshould
beadjustedtoopenthedrainportjustlongenoughto
dischargeaccumulatedcondensate.Setthedrainvalve
operatingtimesothatonlyairdischargesattheendofthe
open period. Recommended initial settings are a 1 to 2
seconddrainopeningand30secondsdrainclosedtime.If
liquidstilldischargesastheportisclosing,setthetimerfora
shorter cycle or a longer opening.
timershouldbeadjustedtoopenthedrainportjustlong
enoughtodischargeaccumulatedcondensate.Setthetimer
sothatonlyairdischargesattheendoftheopenperiod.
Dew Point Indicator
(Models RNP75, RNP100, RNP125 and RNP150)
3 4
2
1
5
Drain Timer
(Models RNP75, RNP100, RNP125 and RNP150)
1. Adjustmentknobforthedrainvalveopentime.The
values on the dial correspond to the time in seconds
that the valve is open in each drain cycle.
2. Adjustmentknobforthedrainvalveclosedtime.The
values on the dial correspond to the time in minutes
that the valve is closed in each drain cycle.
3. LEDtoindicatewhenthedrainvalveisopen.
4. Draintestbutton.Whenthebuttonispressed,the
drainvalveopensforthetimecorrespondingtothe
setting on item 1.
5.LEDtoindicatewhenthedrainvalveisclosed.