iCommand-Touch Manual
CAP-837 
Parameter 
Value setting/Initial setting/Remarks
Act. damping 
initial 
Specifies the minimum time of the first switch
compressor.
Setting range: 0 
Initial setting: 5s
Deact. damping 
initial 
Specifies the minimum time of the first switch
compressor.
Setting 
range: 0 
Initial setting: 2 s
Act. damping 
subsequent 
Specifies the time prior to switching on further co
pressors (if the pressure continuous to drop after 
having switch on).
Setting range: 1 
Initial setting: 5 s
Deact. damping 
subsequent 
Specifies the minimum time prior to switching on 
further compressors (if the pressure continuous to 
rise after having switched off).
Setting range: 2 
Initial setting: 2 s
Changeover int. 
priority 1 
Time betwe
en the change
compressor with priority 1.
Setting range: 1 
Initial setting: 24 h
Changeover int. 
priority 2 
Time between the changeover of the LLC for the 
compressor with priority 2.
Setting range: 1 
Initial setting: 24 h
Changeover int. 
priority 3 
Time between the changeover of the LLC for the 
compressor with priority 3.
Setting range: 1 
Initial setting: 24 h
iCommand 
47 
Value setting/Initial setting/Remarks
Compressor 
type 
Specifies the minimum time of the first switch
-on of a 
compressor.
Setting range: 0 
– 600 s 
Initial setting: 5s
All 
Specifies the minimum time of the first switch
-off of a 
compressor.
range: 0 
– 60 s 
Initial setting: 2 s
All 
Specifies the time prior to switching on further co
m-
pressors (if the pressure continuous to drop after 
having switch on).
Setting range: 1 
– 600 s 
Initial setting: 5 s
All 
Specifies the minimum time prior to switching on 
further compressors (if the pressure continuous to 
rise after having switched off).
Setting range: 2 
– 60 s 
Initial setting: 2 s
All 
en the change
-over of the LLC for the 
compressor with priority 1.
Setting range: 1 
– 168 h 
Initial setting: 24 h
All 
Time between the changeover of the LLC for the 
compressor with priority 2.
Setting range: 1 
– 168 h 
Initial setting: 24 h
All 
Time between the changeover of the LLC for the 
compressor with priority 3.
Setting range: 1 
– 168 h 
Initial setting: 24 h
All 
 iCommand – Touch 
iCommand 
- Touch 
Compressor 
State 
Editable 
Editable 
Editable 
Editable 
Editable 
Editable 
Editable 