iCommand-Touch Manual
CAP-837 
Fig. 51: "LLC configuration" screen 
(Part 1/2) 
Fig. 52: "LLC configuration" screen 
(Part 2/2) 
Parameter 
Value setting/Initial setting/Remarks
Lead lag control 
Indicates if and how the communication for 
function should be done (or if a LLC module is avai
able). 
Setting range:
 
No (no LLC)
 
Digital (LLC via expansion module)
 
RS485 (LLC via RS485 connection)
 
When selecting "Digital" a LLC module is 
expected at address 2
Initial setting: No
Baud rate  Baud rate 
for communication on LLC via RS485
Setting range: 4800 / 9600 / 19200 / 38400 / 57600 / 
115200 
Initial setting: 19200
Change immedi-
ately 
Specifies if the LLC series rotates immediately after 
the change interval is completed (recommended) or 
only when the switch
reached. Warning: If No, the change interval can be 
iCommand 
45 
Individual settings (e.g. switch-on times, switch-
off and change inte
vals) can be set in the "LLC configuration" (Fig. 
50
Using the   
button the second part of the menu can be screen 
(Fig. 52) accessed. 
Value setting/Initial setting/Remarks
Compressor 
type 
Indicates if and how the communication for 
the LLC 
function should be done (or if a LLC module is avai
l-
Setting range:
No (no LLC)
Digital (LLC via expansion module)
RS485 (LLC via RS485 connection)
When selecting "Digital" a LLC module is 
expected at address 2
Initial setting: No
All 
for communication on LLC via RS485
Setting range: 4800 / 9600 / 19200 / 38400 / 57600 / 
Initial setting: 19200
All 
Specifies if the LLC series rotates immediately after 
the change interval is completed (recommended) or 
only when the switch
-on or switch-off threshold is 
reached. Warning: If No, the change interval can be 
All 