iCommand-Touch Manual

CAP-837
Parameter
Value setting/Initial setting/Remarks
Max. no. of
motor starts
During activated switch cycles monitoring:
motor starts per hour.
Setting range: 1 –
60 /h
Initial setting: depends on compressor type
Lead lag
control
During operation with an external LLC (as LLC slave) Local pressure tole
ance is ignored. However,
with the LLC -
OK function and Remote Load / Idling (=external load r
quirement) are required to trigger via digital signals. Furthermore, the p
rameter "Remote Load / Idling" must be set to "Yes" (see above)
Setting range: Yes/No
Initial setting: No
iCommand
27
Value setting/Initial setting/Remarks
During activated switch cycles monitoring:
maximum amount of permitted
60 /h
Initial setting: depends on compressor type
During operation with an external LLC (as LLC slave) Local pressure tole
r-
ance is ignored. However,
maximum pressure is still monitored. Two inputs
OK function and Remote Load / Idling (=external load r
e-
quirement) are required to trigger via digital signals. Furthermore, the p
a-
rameter "Remote Load / Idling" must be set to "Yes" (see above)
.
iCommand – Touch
iCommand
- Touch
Com-
pressor
type
State
All Editable
maximum pressure is still monitored. Two inputs
All Editable