iCommand-Touch Manual
CAP-837 
2.7.6 
"Factory settings" menu
Fig. 47: "Factory settings" screen 
Parameter 
Value setting/Initial setting/Remarks
Start-up time 
Specifies the start
Setting range: 3 
Initial setting: depending on compressor type
Off time 
Specifies the minimum run
switch off of the compressor. This value is also used 
during restart delays after power failure.
Setting range: 0 
Initial setting: 120 s
Run on time 
Specifies the run on time of the compressor in 
automatic opera
switching operations.
Setting range: 10 
Initial setting: depending on compressor type
Final temperature 
min. 
Specifies the minimum start temperature of the 
compressor
Setting range: 32 
Initial setting: 41 °F
Final temp. 
warning 
Specifies the upper threshold for the compressors final 
temperature.
Setting range: 194 
Initial setting: 221 °F
Final temperature 
limited to 
Specifies the switch
compressors final temperature (fault).
Setting range: 212 
Initial setting: 230 °F
iCommand 
43 
"Factory settings" menu
In the "Factory settings" menu the operating times and final compre
sor temperature are displayed. 
Value setting/Initial setting/Remarks
Compressor 
type 
Specifies the start
-up time of the motor. 
Setting range: 3 
– 30 s 
Initial setting: depending on compressor type
All 
Specifies the minimum run
 on time during manual 
switch off of the compressor. This value is also used 
during restart delays after power failure.
Setting range: 0 
– 120 s 
Initial setting: 120 s
All 
Specifies the run on time of the compressor in 
automatic opera
tion or when exceeding the specified 
switching operations.
Setting range: 10 
– 3600 s 
Initial setting: depending on compressor type
All 
Specifies the minimum start temperature of the 
Setting range: 32 
– 50 °F 
Initial setting: 41 °F
All 
Specifies the upper threshold for the compressors final 
temperature.
Setting range: 194 
– 230 °F 
Initial setting: 221 °F
All 
Specifies the switch
-off threshold for the  
compressors final temperature (fault).
Setting range: 212 
– 248 °F 
Initial setting: 230 °F
All 
 iCommand – Touch 
iCommand 
- Touch 
In the "Factory settings" menu the operating times and final compre
s-
Compressor 
State 
Display 
Display 
Display 
Display 
Display 
Display 