Acceptable Mounting
Unacceptable Mounting
•
  Concrete Anchor Bolts 
•  Threaded Rod or Floor Stud 
•  Steel flooring or supports (provided unit 
is bolted down and isolator pads are 
used) 
•
  Skid Mounted 
•  Unanchored 
•  Bare Floor (no vibration pads) 
Table (2) Compressor mounting methods 
If you wish to utilize an installation method other than the approved methods described in 
Table (2), please contact your local distributor. FS Curtis neither states as fact, nor implies 
that the above list of Acceptable/Unacceptable mounting is all-inclusive. Contact your local 
distributor for more information. 
Step 4 – Install Vibration Isolator pads and mount the compressor 
Exposure to excessive vibrations can significantly shorten the life of the compressor. FS 
Curtis highly recommends mounting the unit on vibration isolator pads and the compressor 
should NEVER be operated without being securely fastened to the ground.  
Using a level, please check for proper alignment of the compressor. Uneven installation will 
unbalance the compressor leading to excessive noise, vibrations, and wear. Place a steel 
shim between the concrete and vibration pads and shim down as necessary for leveling. Level 
the compressor so it can be bolted down securely. Before tightening the bolts, check to see 
that all four feet are resting on the foundation. See fig (5) for mounting instructions for a floor 
stud, and see fig (6) for mounting instructions for an anchor bolt. 
FLANGE NUT
Leave loose & lock
with a back-up nut
RECEIVER FOOT
ISOLATOR BACKING
PLATE OR SHIMS IF
NECESSARY
ISOLATOR
ANCHORED
FLOOR
STUD
FLANGE NUT
Leave loose & lock
with a back-up nut
RECEIVER FOOT
ISOLATOR BACKING
PLATE OR SHIMS IF
NECESSARY
ISOLATOR
ANCHORED
FLOOR
STUD
Fig. (5) Anchored Floor Stud installation   