User Manual

22
Criteria for the Proper Selection of String Fuses
Criteria for the
Proper Selec-
tion of String
Fuses
Effects of
Using Under-
rated Fuses
With underrated fuses, the nominal current rating of the fuse is less than
the short circuit current of the solar module.
Effect:
The fuse may blow under intensive irradiance conditions.
Fuse Recom-
mendations -
Application
Example
NOTE! Only select fuses whose nominal voltage is higher or
equal to the max. input voltage of the inverter being used.
Example: Maximum short circuit current (I
SC
) of the solar module = 5.75 A
According to the criteria for selecting the correct fuse, the fuse must have
a nominal current greater than 1.56 times the short circuit current:
5.75 A x 1.56 = 8.97 A
The fuse that should be selected according to the ‘Fuses’ table: KLK D 9
with 9.0 A and 600 V AC / DC
General The use of string fuses in the Fronius String Control 250/25 also adds
fuse protection to the solar modules.
A crucial factor for the fuse protection of solar modules is the maximum
short circuit current I
SC
of the respective solar module.
The following criteria must be fulfilled for each solar module string when
using fuse protection:
-I
N
> 1.56 x I
SC
-I
N
< 2.00 x I
SC
-V
N
max. input voltage of inverter being used:
FRONIUS CL....................................... 600 V DC
I
N
....... Nominal current rating of fuse
I
SC
..... short circuit current for standard test conditions (STC) according to
solar module data sheet
V
N
..... Nominal voltage rating of fuse
NOTE! The string fuse size must not be greater than the maxi-
mum fuse current rating of the PV module as provided on the PV
module manufacturers data sheet. If no maximum fuse size is
indicated, please contact the PV module manufacturer.