INPUT DA TA
DC Input Voltage Range 0 ... 600 V
Max. Input Voltage 600 V
Max. number of DC Input Terminals 25
Admissible Conductor Size (DC Input Terminals) 12-8 AWG, Copper, solid and stranded conductors
Number of measuring channels 5
Fused inputs per measuring channel 5
Max. continuous DC current per measuiring channel 50 A
Max. Fuse Size (10 x 38 class CC fuse) 20 A, 600 V
No. Grounding Terminals 25
Admissible Conductor Size (GND terminals) 12-6 AWG, Copper and Aluminum, solid and stranded conductors
PV-Array Con guration positive or negative grounding
OUTPUT DATA (TO FRONIUS CL)
Max. continuous DC Current 250 A
Admissible conductor size (DC Output) 350 MCM
Max. number of conductors per output pole 2
DC Terminals 2x M12 lug (double hole)
GND Terminals 2x M12 lug (double hole)
GENERAL DATA
Enclosure Type Type 3R
Unit Dimensions (W x H x D) 27.6 x 19.5 x 5.0 inch (700 x 496 x 127 mm)
Unit Weight 26.5 lbs (12 kg)
Admissible Ambient Temperature -13 ... +140°F (-25 ... +60°C)
Rel. Humidity 0 ... 95 % (non condensing)
Housing Material Powder Coated Aluminum (standard)
Power Supply via RS485, optional UL listed Class 2 (12Vdc)
Compliance UL 1741-2005, ANSI/IEEE C62.41, FCC Part 15 B,
NEC Article 690, C22. 2 No. 107.1-01 (September 2001)
COMMUNICATION
Protocol Type Solar Net, RS485
Connectors 2x RJ45 plugs or 2x 8-pole pressure type terminals