58
Trip Limits NLMON (127 V) Trip Limits NLMON (120 V)
U
AC
[V] Clearing Time [s]
Clearing Time [cyl]
U
AC
[V] Clearing Time [s]
Clearing Time [cyl]
U < 50% 64 0.16
9
60 0.16
9
50 ≤ U < 88 % 112 2
118
106 2
118
110 < U < 120 % 139 1
58
132 1
58
U ≥ 120 % 152 0.16
9
144 0.16
9
U
Imin
adjustable 60 - 121 0.016 - 21.0
1 - 1258
60 - 114 0.016 - 21.0
1 - 1258
U
Imax
adjustable 133 - 152 0.016 - 21.0
1 - 1258
126 - 152 0.016 - 21.0
1 - 1258
U
Omax
adjustable 133 - 152 0.016 - 4.25
1 - 255
126 - 152 0.016 - 4.25
1 - 255
U
Omin
adjustable 60 - 121 0.016 - 4.25
1 - 255
60 - 114 0.016 - 4.25
1 - 255
Frequency (for all setups)
F [Hz] Clearing Time [s]
Clearing Time [cyl]
F
Imax
+ 0.5 > 60.5 0.16
9
F
Omax
+ 2.0 > 62.0 0.16
9
F
Imin
- 0.7 < 59.3 0.16
9
F
Omin
- 3.0 < 57.0 0.16
9
F
Imin
adjustable 45.00 -
65.00
0.016 - 600
1 - 35928
F
Imax
adjustable 45.00 -
65.00
0.016 - 600
1 - 35928
F
Omin
adjustable 45.00 -
65.00
0.016 - 600
1 - 35928
F
Omax
adjustable 45.00 -
65.00
0.016 - 600
1 - 35928
Accuracy
Voltage trip limit accuracy +/- 1.0 % of U
nom
Frequency trip limit accuracy +/- 0.05 Hz
Trip time accuracy +/- 16.7 ms (1 cycle)