Installation Guide

33
Setup 440N Trip Limit 254V Setup 440N Trip Limit NL-Mon 254V
U
AC
[V] Clearing Time [s]
Clearing Time [cyl]
U
AC
[V] Clearing Time [s]
Clearing Time [cyl]
U < 50% 127 0.16
9
127 0.16
9
50 U < 88 % 225 2
118
225 2
118
110 < U < 120 % 280 1
58
280 1
58
U 120 % 305 0.16
9
305 0.16
9
U
Imin
adjustable
U
Omin
adjustable
120 - 252 0.016 - 21.0
1 - 1260
120 - 252 0.016 - 21.0
1 - 1260
U
Imax
adjustable
U
Omax
adjustable
256 - 322 0.016 - 21.0
1 - 1260
256 - 322 0.016 - 21.0
1 - 1260
Setup 480N Trip Limit 277V Setup 480N Trip Limit NL-Mon 277V
U
AC
[V] Clearing Time [s]
Clearing Time [cyl]
U
AC
[V] Clearing Time [s]
Clearing Time [cyl]
U < 50% 139 0.16
9
139 0.16
9
50 U < 88 % 245 2
118
245 2
118
110 < U < 120 % 302 1
58
305 1
58
U 120 % 322 0.16
9
332 0.16
9
U
Imin
adjustable
U
Omin
adjustable
120 - 275 0.016 - 21.0
1 - 1260
120 - 275 0.016 - 21.0
1 - 1260
U
Imax
adjustable
U
Omax
adjustable
279 - 322 0.016 - 21.0
1 - 1260
279 - 322 0.016 - 21.0
1 - 1260
Setup 50Hz/50HN Trip Limit 127V Setup 50Hz/50HN Trip Limit NL-Mon 127V
U
AC
[V] Clearing Time [s]
Clearing Time [cyl]
U
AC
[V] Clearing Time [s]
Clearing Time [cyl]
U < 50% 64 0.16
8
64 0.16
8
50 U < 88 % 112 2
100
112 2
100
110 < U < 120 % 139 1
50
139 1
50
U 120 % 152 0.16
8
152 0.16
8
U
Imin
adjustable
U
Omin
adjustable
60 - 132 0.020 - 21.0
1 - 1050
60 - 132 0.020 - 21.0
1 - 1050
U
Imax
adjustable
U
Omax
adjustable
126 - 166 0.020 - 21.0
1 - 1050
126 - 152 0.016 - 21.0
1 - 1050