Installation Guide
32
Field Adjustable Trip Points
Setup 208/208N Trip Limit 120V Setup 208/208N Trip Limit NL-Mon 120V
U
AC
[V] Clearing Time [s]
Clearing Time [cyl]
U
AC
[V] Clearing Time [s]
Clearing Time [cyl]
U < 50% 60 0.16
9
60 0.16
9
50 ≤ U < 88 % 106 2
118
106 2
118
110 < U < 120 % 132 1
58
132 1
58
U ≥ 120 % 144 0.16
9
144 0.16
9
U
Imin
adjustable
U
Omin
adjustable
60 - 119 0.016 - 21.0
1 - 1260
60 - 119 0.016 - 21.0
1 - 1260
U
Imax
adjustable
U
Omax
adjustable
121 - 166 0.016 - 21.0
1 - 1260
121 - 152 0.016 - 21.0
1 - 1260
Setup 220/220N Trip Limit 120V
Setup BR/BR N Trip Limit 127V
Setup 208/208N Trip Limit NL-Mon 127V
Setup BR/BR N Trip Limit NL-Mon 127V
U
AC
[V] Clearing Time [s]
Clearing Time [cyl]
U
AC
[V] Clearing Time [s]
Clearing Time [cyl]
U < 50% 64 0.16
9
64 0.16
9
50 ≤ U < 88 % 112 2
118
112 2
118
110 < U < 120 % 139 1
58
139 1
58
U ≥ 120 % 152 0.16
9
152 0.16
9
U
Imin
adjustable
U
Omin
adjustable
60 - 126 0.016 - 21.0
1 - 1260
60 - 126 0.016 - 21.0
1 - 1260
U
Imax
adjustable
U
Omax
adjustable
128 - 166 0.016 - 21.0
1 - 1260
128 - 152 0.016 - 21.0
1 - 1260
Setup 240/240N Trip Limit 138V Setup 240/240N Trip Limit NL-Mon 120V
U
AC
[V] Clearing Time [s]
Clearing Time [cyl]
U
AC
[V] Clearing Time [s]
Clearing Time [cyl]
U < 50% 69 0.16
9
60 0.16
9
50 ≤ U < 88 % 122 2
118
106 2
118
110 < U < 120 % 152 1
58
132 1
58
U ≥ 120 % 166 0.16
9
144 0.16
9
U
Imin
adjustable
U
Omin
adjustable
60 - 137 0.016 - 21.0
1 - 1260
60 - 119 0.016 - 21.0
1 - 1260
U
Imax
adjustable
U
Omax
adjustable
140 - 166 0.016 - 21.0
1 - 1260
121 - 152 0.016 - 21.0
1 - 1260