Wallmaster Service Manual (2010)
REFRIGERANT SYSTEM DIAGNOSIS COOLING
REFRIGERANT SYSTEM DIAGNOSIS HEATING
  Low Load Conditions    High Load Conditions    Low Load Conditions    High Load Conditions 
  Low Air Flow Across    High Air Flow Across    Refrigerant System       Low Air Flow Across     
  Indoor Coil  Indoor Coil    Restriction  Outdoor Coil 
  Refrigerant System     Reversing Valve not     Reversing Valve not   
Overcharged
  Restriction  Fully Seated  Fully Seated 
  Undercharged  Overcharged 
Non-Condensables (air)
Undercharged System
  Moisture in System       Defective Compressor       Defective Compressor     
  LOW SUCTION PRESSURE    HIGH SUCTION PRESSURE   LOW HEAD PRESSURE    HIGH HEAD PRESSURE 
  LOW SUCTION PRESSURE    HIGH SUCTION PRESSURE   LOW HEAD PRESSURE    HIGH HEAD PRESSURE 
PROBLEM PROBLEM PROBLEM PROBLEM
PROBLEM PROBLEM PROBLEM PROBLEM
  Low Air Flow Across    Outdoor Ambient Too High    Refrigerant System  Outdoor Ambient Too High   
  Outdoor Coil     for Operation in Heating  Restriction     For Operation In Heating     
  Refrigerant System    Reversing Valve not     Reversing Valve not  Low Air Flow Across   
  Restriction    Fully Seated     Fully Seated  Indoor Coil   
  Undercharged    Overcharged 
  Defective Compressor 
  Undercharged  Overcharged 
  Moisture in System  Defective Compressor 
Non-Condensables (air)
in System
TROUBLESHOOTING CHART - COOLING
TROUBLESHOOTING CHART - HEATING (HEAT PUMP)
39