Product Profile (2020)
Table Of Contents
4
CHASSIS SPECIFICATIONS
Power Cord/Heater Ratings
230/208V ELECTRIC HEATER RATING
(CONFIGURATION BASED ON POWER CORD)
POWER CORD # VOLTAGE BRANCH CKT AMPS MCA WATTS
PXPCFA23015 230/208 15 13.9 2500
PXPCFA23020 230/208 20 19.9 3600
PXPCFA23030* 230/208 30 27.5 5000
PXPCFA26515 265V 15 12.0 2500
PXPCFA26515
1
265V 15 7.3 1500
PXPCFA26520 265V 20 16.8 3500
PXPCFA26530* 265V 25 23.8 5000
*Cannot be used on PVH09K3FA
1
Data for Model PVH09R
PXPCFA23020 comes standard on PTAC
PVH Series Cooling with Heat Pumps
Model PVH09K PVH12K PVH09R PVH12R
PERFORMANCE DATA:
Cooling Capacity Btu 9600/9400 12000/11800 9600 12000
Cooling Capacity Min./Max. Btu 6462 – 12099 7929 – 17142 6462 – 12099 7929 – 17142
Cooling Watts 815/800 1050/1035 800 1040
Energy Efciency Ratio EER 11.8/11.8 11.4/11.4 12.0 11.5
Reverse Heating Capacity Btu 8200/8500 11600/11800 8500 11800
Reverse Heating Capacity Min./Max. Btu 5606 – 11475 6995 – 16187 5606 – 11475 6995 – 16187
Heating Watts 710/685 970/950 710 970
COP 3.51/3.51 3.57/3.58 3.51 3.57
Moisture Removal Pts./Hr. 1.4 1.9 1.2 2.4
Sensible Heat Ratio 80% 78% 82.7% 73.7%
ELECTRICAL DATA:
Voltage (1 PHASE, 60 Hz) 230/208 230/208 265 265
Volt Range 253 – 187 253 – 187 292 – 239 292 – 239
Current Amps 4.4/4.5 4.5/5.0 3.8 4.7
Reverse Heat Amps 4.0/4.1 4.6/4.9 3.6 4.3
Power Factor 0.80 0.96 0.82 0.90
Compressor LRA N/A N/A N/A N/A
Compressor RLA 3.2 4.1 4.2 6.2
Outdoor Fan Motor HP 0.06 0.09 0.06 0.09
AIRFLOW DATA:
Indoor CFM, HIGH 400 470 400 470
Indoor CFM, LOW 250 360 290 360
Vent CFM UP TO 52 UP TO 52 UP TO 52 UP TO 52
PHYSICAL DATA:
Sleeve Dimensions H x W x D
16"x 42"x 13
3
/4" (all models)
Dimensions with front H x W x D
16"x 42"x 21
1
/2" (all models)
Cut Out Dimensions H x W
16
1
/4"x 42
1
/4" (all models)
Net Weight Lbs. 114 120 115 120
Shipping Weight Lbs. 136 142 137 142
R-410A Charge Oz. 30.34 32.80 32.10 32.80
Warning: Coastal Region Installations.
Friedrich Air Conditioning recommends that owners take necessary precautions to protect the interior space, furnishings, and hardware
from corrosion when installing make-up air products in coastal applications. Our FreshAire PTAC delivers up to 52 CFM of direct outside
make-up air into the space. If installed within 2 miles of a body of salt water, due to the high salt content of coastal air and the high latent
load of the make-up air, premature corrosion will occur naturally on non-protected items. Friedrich Air Conditioning is not responsible for
premature corrosion resulting from the use of make-up air products.
Due to continuing research in new energy-saving technology, specifications are subject to change without notice. Warranty limited to
installations in the United States, Puerto Rico, Mexico and Canada only. See warranty documentation for full details.