Service and Parts Manual (2018, 2019, 2020, 2021, 2022)
Table Of Contents
- INTRODUCTION
- Important Safety Information
- Personal Injury Or Death Hazards
- Operation of Equipment in During Construction
- Typical Unit Components and Dimensions
- Model Number Reference Guide
- Serial Number Reference Guide
- Product Features
- General Specifications 9-12k Heat Pump Models
- Electrical Data
- Function and Control
- Buttons and Display
- Temperature Definition
- System Basic Function
- 1) Cooling Mode
- 2) Heating Mode
- 3) Room Freeze Protection (AUTO HEATING)
- 4) Temperature Sensor Open Circuit or Short Circuit Protection
- 5) Power cut protection
- 6) Compressor and DC-inverter features
- 7) Smart fresh air system
- Advanced Functions
- Advanced Settings
- Memory Function
- FD Control (front-desk control) & 24V REMOTE THERMOSTAT
- Protection Functions
- System Configuration Fresh Air Vent Control
- Digital Control User Input Configuration
- Settings- Detailed Configurations
- Refrigeration Sequence Of Operation
- Refrigerant System Diagram
- PTAC Installation Recommendations
- Wall Sleeve Installation Instructions (PDXWS)
- Alternate Wall Installations
- PXDR10 Drain Kit Installation
- External Drain
- PXGA Standard Grille
- Chassis Install
- Remote Control Thermostat Installation
- Front Desk Control Terminal
- Final Inspection & Start-up Checklist
- Remove Chassis
- Remove User Interface
- Open Electrical Control Box
- Remove Main PCB (logic) Board
- Remove Power Cord
- Remove Power PCB
- Remove IPM PCB (Inverter Board)
- Remove Blower Wheel (Inside Fan)
- Remove Blower Wheel Motor (Inside Fan)
- Remove Heating Element
- Remove Freshaire Components
- Remove Outdoor Fan
- Remove Reversing valve Solenoid
- Refrigerant Charging
- Undercharged Refrigerant Systems
- Overcharged Refrigerant Systems
- Restricted Refrigerant System
- Sealed System Method of Charging/ Repairs
- Hermetic Components Check
- Reversing Valve Description And Operation
- Testing The Reversing Valve Solenoid Coil
- Checking The Reversing Valve
- Touch Test Chart : To Service Reversing Valves
- Compressor Checks
- Compressor Replacement
- Compressor Replacement -Special Procedure in Case of Compressor Burnout
- Check Indoor Fan Motor
- Check Outdoor Fan Motor
- Check Fan Motor Capacitors
- Main PCB (logic) Board Connector Identification
- Power PCB (Power Board) Connector Identification
- Basic Troubleshooting
- Error code and solutions
- Unit Does Not Operate
- Check Electric Heater Control
- Check Thermistors
- Check Thermistors -Resistance Table of Thermistors (5K)
- Check Thermistors -Resistance Table of Thermistors (50K)(Compressor Discharge Sensor)
- PARTS CATALOG
29 PB
OPERATION
Settings- Detailed Congurations
This section is about how to set the unit operating parameter, include display temperature unit, Fahrenheit or Celsius, control master, temperature
limit, temperature calibration, display set point or room temperature.
Under OFF mode, hold [Cool] and [Low] two keys at the same time continuously for 5 seconds. This time displays ‘d0’, indicates that system has
entered the senior operation status.
[Cool] key is used to switch parameter code and parameter value;
[UP] or [DOWN] keys are used to switch parameter code or set parameter value; [Power] key is used to save
and exit settings.
Menu NO. Function "Parameter value" Explanation
do Unit of temperature F Fahrenheit (default)
C Celsius
dl Control master p By control panel or IR remote thermostat(default)
r By 24V universal remote thermostat
rE By12V smart wired controller
rF VRPXEMRT2 and VRPXEMWRT2
d2 Max temperature setting d3 to 90°F The Min value is d2 (default 90°F)
d3 Min temperature setting 60°F to d2 The Max value is d3 (default 90°F)
d4 Indoor temperature calibra-
tion
-9°C to 9°C If unit of temperature is changed, calibration should be
done again. If using the default value, it can be ignored.
(default 0°C/O°F)
-9°F to 9°F
d5 Temperature display selec-
tion
O o r 1 0-displays room temperature (default ),
1-displaysset point.
One example:
Setting target:d0(C),d1(r), d2(88),d3(58),d4(-1),d5(1).
Step1: hold [Cool] and [Low] two keys at the same time continuously for 5 seconds. Display:’d0’
Step2: short press [Cool] key. Display: ‘F’(setting d0 has finished)
Step3: short press [Cool] key. Display:’d0’
Step4: short press [UP] key. Display:’d1’
Step5: short press [Cool] key. Display: ‘P’
Step6: short press [UP] or [DOWN] key. Display: ‘r’ (setting d1 has finished)
Step7: short press [Cool] key. Display:’d1’
Step8: short press [UP] key. Display:’d2’
Step9: short press [Cool] key. Display:’90’
Step10: short press [DOWN] key twice. Display:’88’ (setting d2 has finished)
Step11: short press [Cool] key. Display:’d2’
Step12: short press [UP] key. Display:’d3’
Step13: short press [Cool] key. Display:’60’
Step14: short press [UP] key twice. Display:’58’ (setting d3 has finished)
Step15: short press [Cool] key. Display:’d3’
Step16: short press [UP] key. Display:’d4’
Step17: short press [Cool] key. Display:’0’ (setting d4 has finished)
Step18: short press [Power] key to exit.