Installation & Operation Manual (2019, 2020, 2022)

Table Of Contents
4
GeneralSpecifications
Typical Unit Components and Dimensions
WALL SLEEVE
DISCHARGE GRILLE
FILTERS
RETURN AIR GRILLE
OUTDOOR GRILLE
CHASSIS
FRONT COVER
PDXWS Wall Sleeve
Dimensions: 16" H x 42" W x
13-¾" D
Front Cover Dimensions:
16" H x 42" W x 7-¾" D
Cut-Out Dimensions:
16-¼" x 42-¼"
MODEL NUMBER
V
H
09
3 F
Series
PV = Friedrich Digital PTAC
System
E = Cooling with electric heat
H = Heat Pump with Auxiliary Heat
Nominal Capacity
Engineering Digit
Design Series
Chassis
F= FreshAire
07 = 7,000 Btuh
09 = 9,000 Btuh
Voltage
12 = 12,000 Btuh
15 = 15,000 Btuh
Nominal Heater Size (230V or 265V)
3=3kW
K = 230/208V - 1 Ph. - 60 Hz.
R = 265V - 1 Ph. - 60 Hz.
InstallationChecklist
. Inspect all components and accessories for damage before and
after installation.
. Remove the cardboard wall sleeve support and grill weatherboard.
. Check for proper wall sleeve installation in accordance with the wall
sleeve installation instructions.
. Check for a subbase kit or other means of structural support which
is required for ALL installations projecting more than 8" into room.
. Install the recommended Condensate Drain Kits for complete
condensate removal.
. Ensure that the chassis is installed in a 16" highx4'' wide wall sleeve
that is no deeper than 13-¾".A baffle kit is required if the sleeve
exceeds that depth.
. Ensure that chassis and chassis front cover are installed and secured
properly.
. Ensure that drapes,bed,bedspread,furniture,etc DO NOT block
either return or discharge air grilles.
. Inspect the condenser air inlet and outlet for any obstructions
(shrubbery,etc).
. Ensure that 'reset' button is pressed on LCD device(only on cord
connected models).
A