PTAC Wall Sleeve Installation Guide

Deep Wall Installation
If wall is thicker than allowed in the notes in Figure 2, a sheet
metal wall sleeve extension and MUST be used. See
Figure 4 for guidelines to use in fabricating a wall sleeve ex-
tension.
Field Fabricating A Sleeve Extension
The Following points MUST be considered when designing a
wall sleeve extension.
1. Provision must be made to direct excess condensate from
the back of the wall sleeve to the outside of the build-
ing.
2. Air must be mounted to properly direct air
from the condenser.
3. Wall Sleeve Extension design must allow for the proper
mounting of the louvers.
4. Caulking of all potential sites where condensate or external
5. Seal strips must be attached to the outside edge of the
Figure 4. Extended Wall Sleeve and Sealant Locations
IMPORTANT NOTE: The silicone bead MUST extend 3" up
the side of the two
to prevent condensate from
leaking.
42 X 16" Frame, 20 gauge minimum,
painted or aluminium
Sealant inside (4)
bottom corners
Condensate
Notches
Condensate
Drip Panel
(Field
Supplied)
Drip
Edge
Width of wall
Wall Sleeve
Outside Edge
Insulation
6. Condensate notches are clear of sealant so condensate
NOTE: Improper fabrication of a wall sleeve extension will
impair PTAC performance. Regardless of your extended
wall sleeve design, provision MUST be made for proper direc-
Extension Installation
Size wall sleeve extension to frame opening. Secure it to
the
wall sleeve before installing in the wall. Refer to Figure 4
for a
guide for fabrication of a condensate drip panel. Panel MUST
extend the full depth of the wall sleeve and the wall sleeve
extension. Pay particular care in sealing and caulking the panel
where it makes contact with the wall sleeve (see Figure 4 .)
After installation in the wall, secure with fasteners through the
sides. Seal around the sleeve extension with exterior caulking.
Using a good grade of silicone sealant, seal all exposed screw
heads. When installation is complete, outside louver may be
attached to wall sleeve extension.
94993000_00 (1-13)