Service and Parts Manual (2016, 2017, 2018, 2019, 2020, 2021, 2022)
Table Of Contents
- INTRODUCTION
- Important Safety Information
- Personal Injury Or Death Hazards
- Operation of Equipment in During Construction
- Model Number Reference Guide
- Serial Number Reference Guide
- General Specifications 7-9k Electric Heat
- General Specifications 7-9k Heat Pump Models
- General Specifications 12-15k Electric Heat
- General Specifications 12-15k Heat Pump
- Electrical Data
- Function and Control
- Dip Switch Function #1
- Dip Switch Function #2
- Dip Switch Function #3&4
- Dip Switch Function #5&6
- Dip Switch Function #7
- Refrigeration Sequence Of Operation
- Refrigerant System Diagram
- Remove The Chassis
- Remove The Chassis
- Indoor Motor, Wheel, & Heating Element Assembly
- Outdoor Motor, Blade, & Shroud Assembly
- Electronic Board & Electrical Component Replacement
- PTAC Installation Recommendations
- Wall Sleeve Installation Instructions (PDXWS)
- Alternate Wall Installations
- PXDR10 Drain Kit Installation
- External Drain
- PXGA Standard Grille
- Electrical Wiring for 265 Volt Models
- Chassis Install Preparation
- Chassis Installation
- How To Connect
- Thermostat
- Final Inspection & Start-up Checklist
- Refrigerant Charging
- Undercharged Refrigerant Systems
- Overcharged Refrigerant Systems
- Restricted Refrigerant System
- Sealed System Method of Charging/ Repairs
- Hermetic Components Check
- Reversing Valve Description And Operation
- Testing The Reversing Valve Solenoid Coil
- Checking The Reversing Valve
- Touch Test Chart : To Service Reversing Valves
- Compressor Checks
- Compressor Replacement -Special Procedure in Case of Compressor Burnout
- PCB Printed Diagram Board 1
- PCB Printed Diagram Board 2
- Testing Component Voltage at Electronic Control Board
- Testing Line Voltage
- Basic Troubleshooting
- Error Codes
- Malfunction of Temperature Sensor
- Maintenance Method for Normal Malfunction
- PDE07
- PDH07
- PDE09, PDE12, PDE15
- PDH09, PDH12, PDH15
- PARTS CATALOG
- PDE07K, PDE07R, PDE09K, PDE09R, PDE12K, PDE12R, PDE15K, PDE15R
- PDH07K, PDH07R, PDH09K, PDH09R, PDH12K, PDH12R, PDH15K, PDH15R
- Reference Sheet of Celsius and Fahrenheit
- Resistance Table of Indoor Ambient Temperature Sensor (15K)
- Resistance Table of Tube Temperature Sensors for Indoor and Outdoor(20K)
- Resistance Table of Discharge Temperature Sensor for Outdoor(50K)
82 PB
R-410A SEALED SYSTEM REPAIRS
Sealed System Method of Charging/ Repairs
BURN HAZARD
Proper safety procedures must be followed,
and proper protective clothing must be worn
when working with a torch.
Failure to follow these procedures could
result in moderate or serious injury.
WARNING
FREEZE HAZARD
Proper safety procedures must be followed,
and proper protective clothing must be worn
when working with liquid refrigerant.
Failure to follow these procedures could
result in minor to moderate injury.
CAUTION
The refrigerant cycle is critically charged. The only acceptable method for charging the sealed system is the
Weighed in Charge Method.
The weighed in method should always be used whenever a charge is removed from a unit such as for a leak
repair, compressor replacement, or when there is no refrigerant charge left in the unit. To charge by this method,
requires the following steps:
1. Install a piercing valve to remove refrigerant from the sealed system. (Piercing valve must be removed from
the system before recharging.)
2. Recover Refrigerant in accordance with EPA regulations.
3. Install a process tube to sealed system.
4. Make necessary repairs to system.
5. Evacuate system to 200 microns or less.
6. Weigh in refrigerant with the property quantity of R-410A refrigerant.
7. Start unit, and verify performance.
8. Crimp the process tube and solder the end shut.