Service and Parts Manual (2016, 2017, 2018, 2019, 2020, 2021, 2022)
Table Of Contents
- INTRODUCTION
- Important Safety Information
- Personal Injury Or Death Hazards
- Operation of Equipment in During Construction
- Model Number Reference Guide
- Serial Number Reference Guide
- General Specifications 7-9k Electric Heat
- General Specifications 7-9k Heat Pump Models
- General Specifications 12-15k Electric Heat
- General Specifications 12-15k Heat Pump
- Electrical Data
- Function and Control
- Dip Switch Function #1
- Dip Switch Function #2
- Dip Switch Function #3&4
- Dip Switch Function #5&6
- Dip Switch Function #7
- Refrigeration Sequence Of Operation
- Refrigerant System Diagram
- Remove The Chassis
- Remove The Chassis
- Indoor Motor, Wheel, & Heating Element Assembly
- Outdoor Motor, Blade, & Shroud Assembly
- Electronic Board & Electrical Component Replacement
- PTAC Installation Recommendations
- Wall Sleeve Installation Instructions (PDXWS)
- Alternate Wall Installations
- PXDR10 Drain Kit Installation
- External Drain
- PXGA Standard Grille
- Electrical Wiring for 265 Volt Models
- Chassis Install Preparation
- Chassis Installation
- How To Connect
- Thermostat
- Final Inspection & Start-up Checklist
- Refrigerant Charging
- Undercharged Refrigerant Systems
- Overcharged Refrigerant Systems
- Restricted Refrigerant System
- Sealed System Method of Charging/ Repairs
- Hermetic Components Check
- Reversing Valve Description And Operation
- Testing The Reversing Valve Solenoid Coil
- Checking The Reversing Valve
- Touch Test Chart : To Service Reversing Valves
- Compressor Checks
- Compressor Replacement -Special Procedure in Case of Compressor Burnout
- PCB Printed Diagram Board 1
- PCB Printed Diagram Board 2
- Testing Component Voltage at Electronic Control Board
- Testing Line Voltage
- Basic Troubleshooting
- Error Codes
- Malfunction of Temperature Sensor
- Maintenance Method for Normal Malfunction
- PDE07
- PDH07
- PDE09, PDE12, PDE15
- PDH09, PDH12, PDH15
- PARTS CATALOG
- PDE07K, PDE07R, PDE09K, PDE09R, PDE12K, PDE12R, PDE15K, PDE15R
- PDH07K, PDH07R, PDH09K, PDH09R, PDH12K, PDH12R, PDH15K, PDH15R
- Reference Sheet of Celsius and Fahrenheit
- Resistance Table of Indoor Ambient Temperature Sensor (15K)
- Resistance Table of Tube Temperature Sensors for Indoor and Outdoor(20K)
- Resistance Table of Discharge Temperature Sensor for Outdoor(50K)
81 PB
R-410A SEALED SYSTEM REPAIRS
Restricted Refrigerant System
Troubleshooting a restricted refrigerant system can be difcult. The following procedures are the more common problems
and solutions to these problems. There are two types of refrigerant restrictions: Partial restrictions and complete restrictions.
A partial restriction allows some of the refrigerant to circulate through the system.
With a complete restriction there is no circulation of refrigerant in the system.
Restricted refrigerant systems display the same symptoms as a “low-charge condition.”
When the unit is shut off, or the compressor disengages, the gauges may equalize very slowly.
A quick check for either condition begins at the evaporator. With a partial restriction, there may be gurgling sounds at the
metering device entrance to the evaporator. The evaporator in a partial restriction could be partially frosted or have an ice ball
close to the entrance of the metering device. Frost may continue on the suction line back to the compressor.
Often a partial restriction of any type can be found by feel, as there is a temperature difference from one side of the restriction
to the other.
With a complete restriction, there will be no sound at the metering device entrance. An amperage check of the compressor
with a partial restriction may show normal current when compared to the unit speci cation. With a complete restriction the
current drawn may be considerably less than normal, as the compressor is running in a deep vacuum (no load.) Much of the
area of the condenser will be relatively cool since most or all of the liquid refrigerant will be stored there.
The following conditions are based primarily on a system in the cooling mode.
Figure 603 (Restricted System)