Service and Parts Manual (2016, 2017, 2018, 2019, 2020, 2021, 2022)
Table Of Contents
- INTRODUCTION
- Important Safety Information
- Personal Injury Or Death Hazards
- Operation of Equipment in During Construction
- Model Number Reference Guide
- Serial Number Reference Guide
- General Specifications 7-9k Electric Heat
- General Specifications 7-9k Heat Pump Models
- General Specifications 12-15k Electric Heat
- General Specifications 12-15k Heat Pump
- Electrical Data
- Function and Control
- Dip Switch Function #1
- Dip Switch Function #2
- Dip Switch Function #3&4
- Dip Switch Function #5&6
- Dip Switch Function #7
- Refrigeration Sequence Of Operation
- Refrigerant System Diagram
- Remove The Chassis
- Remove The Chassis
- Indoor Motor, Wheel, & Heating Element Assembly
- Outdoor Motor, Blade, & Shroud Assembly
- Electronic Board & Electrical Component Replacement
- PTAC Installation Recommendations
- Wall Sleeve Installation Instructions (PDXWS)
- Alternate Wall Installations
- PXDR10 Drain Kit Installation
- External Drain
- PXGA Standard Grille
- Electrical Wiring for 265 Volt Models
- Chassis Install Preparation
- Chassis Installation
- How To Connect
- Thermostat
- Final Inspection & Start-up Checklist
- Refrigerant Charging
- Undercharged Refrigerant Systems
- Overcharged Refrigerant Systems
- Restricted Refrigerant System
- Sealed System Method of Charging/ Repairs
- Hermetic Components Check
- Reversing Valve Description And Operation
- Testing The Reversing Valve Solenoid Coil
- Checking The Reversing Valve
- Touch Test Chart : To Service Reversing Valves
- Compressor Checks
- Compressor Replacement -Special Procedure in Case of Compressor Burnout
- PCB Printed Diagram Board 1
- PCB Printed Diagram Board 2
- Testing Component Voltage at Electronic Control Board
- Testing Line Voltage
- Basic Troubleshooting
- Error Codes
- Malfunction of Temperature Sensor
- Maintenance Method for Normal Malfunction
- PDE07
- PDH07
- PDE09, PDE12, PDE15
- PDH09, PDH12, PDH15
- PARTS CATALOG
- PDE07K, PDE07R, PDE09K, PDE09R, PDE12K, PDE12R, PDE15K, PDE15R
- PDH07K, PDH07R, PDH09K, PDH09R, PDH12K, PDH12R, PDH15K, PDH15R
- Reference Sheet of Celsius and Fahrenheit
- Resistance Table of Indoor Ambient Temperature Sensor (15K)
- Resistance Table of Tube Temperature Sensors for Indoor and Outdoor(20K)
- Resistance Table of Discharge Temperature Sensor for Outdoor(50K)
61 PB
INSTALLATION
Wall Sleeve Installation Instructions (PDXWS)
6
Wall Sleeve Installation Instructions (PDXWS)
NOTE: Insure that the unit is only installed in a wall structurally adequate to support the unit including the sleeve, chassis and accessories. If the sleeve
projects more than 8" into the room, a subbase or other means of support MUST be used. Please read these instructions completely before
attempting installation.
For Deep Wall Installation (Greater than 13 1/4")
See Page 9
The following instructions apply ONLY to walls less than 13 ¼" in depth.
1. The PXDR10 Drain Kit (optional for new construction) see page 10
if applicable, must be installed before the wall sleeve is installed
into the wall.
2. The External Drain (for new construction or unit replacement) see
page 11, if applicable, must be installed before the wall sleeve is
installed into the wall.
3. From inside the building, position the wall sleeve in the opening and
push it into the wall until it protrudes at least ¼” on the outside. Do
not allow sleeve to be pulled. (See Figure 11, Page 10).
4. Position the wall sleeve with a slight tilt towards the outside to
facilitate condensate drainage. It should be level side-to-side and
the front should be ¼ bubble higher than the back.
Figure 3
Typical Wall Sleeve Installation
NOTICE
DO NOT allow any pitch toward the inside.
Flashing on all 4 sides of the opening is recommended.
Potential property damage can occur if instructions are
not followed.
WARNING
Falling Object Hazard
Not following Installation Instructions for
mounting your air conditioner can result
in property damage, injury, or death.
FRP008
20
"
MAX.
16-¼
"
42-¼
"
MIN.
LINTEL TO SUPPORT
MASONRY WALLS
ELECTRICAL
RECEPTACLE
ELECTRICAL
RECEPTACLE
WALL OPENING
WALL SLEEVE
INSULATION
INSULATION
SMOOTH SIDE OF SCREW
CLIP FACING INTO ROOM
NOTE: All 230/208V units are manufactured with a 60” power cord and all 265V units with a 18” power cord.
60
"
MAX.
13-¾
"