Service and Parts Manual (2016, 2017, 2018, 2019, 2020, 2021, 2022)
Table Of Contents
- INTRODUCTION
- Important Safety Information
- Personal Injury Or Death Hazards
- Operation of Equipment in During Construction
- Model Number Reference Guide
- Serial Number Reference Guide
- General Specifications 7-9k Electric Heat
- General Specifications 7-9k Heat Pump Models
- General Specifications 12-15k Electric Heat
- General Specifications 12-15k Heat Pump
- Electrical Data
- Function and Control
- Dip Switch Function #1
- Dip Switch Function #2
- Dip Switch Function #3&4
- Dip Switch Function #5&6
- Dip Switch Function #7
- Refrigeration Sequence Of Operation
- Refrigerant System Diagram
- Remove The Chassis
- Remove The Chassis
- Indoor Motor, Wheel, & Heating Element Assembly
- Outdoor Motor, Blade, & Shroud Assembly
- Electronic Board & Electrical Component Replacement
- PTAC Installation Recommendations
- Wall Sleeve Installation Instructions (PDXWS)
- Alternate Wall Installations
- PXDR10 Drain Kit Installation
- External Drain
- PXGA Standard Grille
- Electrical Wiring for 265 Volt Models
- Chassis Install Preparation
- Chassis Installation
- How To Connect
- Thermostat
- Final Inspection & Start-up Checklist
- Refrigerant Charging
- Undercharged Refrigerant Systems
- Overcharged Refrigerant Systems
- Restricted Refrigerant System
- Sealed System Method of Charging/ Repairs
- Hermetic Components Check
- Reversing Valve Description And Operation
- Testing The Reversing Valve Solenoid Coil
- Checking The Reversing Valve
- Touch Test Chart : To Service Reversing Valves
- Compressor Checks
- Compressor Replacement -Special Procedure in Case of Compressor Burnout
- PCB Printed Diagram Board 1
- PCB Printed Diagram Board 2
- Testing Component Voltage at Electronic Control Board
- Testing Line Voltage
- Basic Troubleshooting
- Error Codes
- Malfunction of Temperature Sensor
- Maintenance Method for Normal Malfunction
- PDE07
- PDH07
- PDE09, PDE12, PDE15
- PDH09, PDH12, PDH15
- PARTS CATALOG
- PDE07K, PDE07R, PDE09K, PDE09R, PDE12K, PDE12R, PDE15K, PDE15R
- PDH07K, PDH07R, PDH09K, PDH09R, PDH12K, PDH12R, PDH15K, PDH15R
- Reference Sheet of Celsius and Fahrenheit
- Resistance Table of Indoor Ambient Temperature Sensor (15K)
- Resistance Table of Tube Temperature Sensors for Indoor and Outdoor(20K)
- Resistance Table of Discharge Temperature Sensor for Outdoor(50K)
11 PB
SPECIFICATIONS
General Specications 7-9k Heat Pump Models
PTAC Heat Pump models
PDH07K PDH07R PDH09K PDH09R
PERFORMANCE DATA:
Cooling Btu 7200/7000 7200 9400/9200 9400
Cooling Watts 550/535 550 775/760 775
Energy Efcient Ratio, Eer 13.0/13.0 13.0 12.1/12.1 12.1
Reverse Heating Btu 6000/5800 6000 8300/8100 8300
Heating Watts 485/470 485 695/675 695
Cop 3.6/3.6 3.6 3.5/3.5 3.5
Moisture Removal (Pints/Hr.) 1.7 1.7 2.1 2.1
Sensible Heat Ratio 0.86 0.86 0.85 0.85
ELECTRICAL DATA:
Voltage(1 PHASE, 60 Hz) 230/208 265 230/208 265
Volt Range 253-187 292-239 253-187 292-239
Current (Amps) 2.7/2.9 2.4 3.7/3.9 3.3
Reverse Heat. Amps 2.4/2.6 2.2 3.4/3.2 3.1
Power Factor 0.97 0.97 0.97 0.97
Compressor LRA 13.0 12.5 19.5 13.5
Compressor RLA 2.5 2.2 3.5 3.0
Outdoor Fan Motor, HP 0.080 0.080 0.080 0.080
AIRFLOW DATA:
Indoor CFM, HIGH 345/315 345 355/325 355
Indoor CFM, LOW 270/255 270 300/275 300
VENT CFM 75 75 75 75
PHYSICAL DATA
Sleeve Dimensions (H x W x D) 16” x 42” x 13 3/4” (all models)
Dimensions with Front (H x W x D) 16”x 42”x 21 1/2” (all models)
Cut Out Dimensions (H x W x D) 16 1/4”x 42 1/4” (all models)
Net Weight (lbs.) 113 112 119 119
Shipping Weight (lbs.) 133 132 139 139
R-410A CHARGE (oz.) 34 34 34 34
Dimensions with Packaging (inches) 17 7/8" x 45" x 25 1/4" (all models)
Figure 202 (General Specs)