PTAC Installation and Operation Manual

5
PTAC Installation Recommendations
    
     
   




  
  
      
    
     

• 

 


• 

   
 


For proper PTAC unit performance and maximum operating life refer to the minimum installation clearances
below:
For PTACs on the ground floor or anytime obstructions are present, use the following guidelines:


Figure1
Figure2
FRP002
PTAC
SHRUB
POLE
FENCE OR WALL
CATPCATP
TYPICAL BUILDING ( PLAN VIEW )
CONDENSING UNIT
12"
36"
36"
36"
36" MIMUMUM, MAJO
R
OBSTRUCTIONS
12" MINIMUM, MINOR
OBSTRUCTIONS
FRP001
THREE OR MORE PTACs
ADJACENT 36" MINIMUM
GROUND FLOOR PTACs
6" MINIMUM FROM GRADE
TWO ADJACENT PTACs
12" MINIMUM
TYPICAL
WINDOW
VIEW: OUTSIDE BUILDING ELEVATION
60" VERTICAL
MIMUMUM
BETWEEN
PTACs
12"
6"
36"
60"