2014 PTAC Product Profile

1110
IMPORTANT NOTE:
The silicone bead MUST extend up
the side of the two anges to prevent
condensate from leaking.
Seal condensate drip pan
to wall sleeve with sealant
on all (4) bottom corners.
Deep Wall Sleeve Installation
Typical Wall Sleeve Installation (PDXWS)
Installation
Note the use of a lintel under the rst course
of bricks above the wall sleeve. Do not use
the wall sleeve as a lintel. The mounting
screw holes shown are to be made by the
installer.
Note: All 230/208V units are manufactured
with a 60" power cord and all 265V units with
an 18" power cord. The receptacle locations
above must be followed to ensure proper
connections.
Architectural Louver Installation (PXAA)
INSTALL ATION
1. Screw a threaded metal stud into each of the
holes at the four corners of the louver.
2. From inside the building, grasp the louver
at the vertical supports and maneuver the
louver through the wall sleeve. Pull towards
you until the threaded studs are inserted into
the four holes of the wall sleeve.
3. While holding the louver with one hand, start
washers and nuts on each of the four studs.
Tighten the nuts securely.
External Drain
PXDR10 DRAIN KIT
Internal Drain Kit Location and Installation (PXDR10)
Accessory Installation
When using an external drain sys-
tem, the condensate is removed
through either of two drain holes
on the back of the wall sleeve.
Select the drain hole which best
meets your drainage situation and
install the drain kit. Seal off the
other with a cover plate.
Place the drain tube through the
gasket and the mounting plate with
the ange toward the wall sleeve.
Attach the drain tube assembly to
one of the two drain holes at the
rear of the wall sleeve. The large
ange on the mounting plate is po-
sitioned at the bottom of the sleeve
facing toward the sleeve. When
the drain tube is positioned at the
desired angle, tighten the screws.
CAUTION
Bodily injury can be caused by louvers
falling from a building during installation. It is
recommended that a safety line be attached
to the louver and an anchor point inside the
building during installation.
FRP008
20
"
MAX.
16-¼
"
42-¼
"
MIN.
LINTEL TO SUPPORT
MASONRY WALLS
ELECTRICAL
RECEPTACLE
ELECTRICAL
RECEPTACLE
WALL OPENING
WALL SLEEVE
INSULATION
INSULATION
SMOOTH SIDE OF SCREW
CLIP FACING INTO ROOM
NOTE: All 230/208V units are manufactured with a 72” power cord and all 265V units with a 20” power cord.
60
"
MAX.
13-¾
"
FRP010
NO
TE: Construct wall opening to comply with all applicable building codes.
MAIN STUDS
JACK STUDS
LINTEL
MOUNTING
SCREW HOLES
NO HOLES IN BOTTOM OF WALL
SLEEVE UNLESS DRAIN KIT IS USED
MAIN STUDS
JACK STUDS
DRAIN TUBE
SIDE VIEW
FRONT VIEW
WALL SLEEVE
OPTIONAL AREA
PREFERRED AREA-
NO FOAM INSULATION
THE DRAIN MUST BE
TED IN THE OPTIONAL
REA, THE FOAM INSULATION
BE CUT AWAY AND
TO ALLOW ACCESS
THE DRAIN.
NUT
MOUNTING
PLATE
GASKET
3"
FRP012
FOAM
GASKET
OVERFLOW
SLOTS
DETAIL B
DETAIL A
COVER
PLATE
FOAM
GASKET
SCREWS
½” O.D. TUBE
MOUNTING
PLATE
NUT
Outside
Edge
Wall Sleeve
Air
Bafes
Condensate Drip
Panel (Field Supplied)
Width of Wall
2"