Brochure
MULTIZONE CONFIGURATION GUIDELINES
MR36TQY3JMA:
FOR (2) ZONES:
Minimum combination must be 50% of
nameplate capacity
FOR (3) ZONES:
Select any combination of (3) indoor
units with no more than (2) 18,000 Btu
indoor units plus (1) other indoor unit.
FOR (4) ZONES:
Select any combination of (4) indoor
units.
Combinations SHOULD NOT:
Exceed the maximum allowable total
indoor unit connected capacity of
48,000 Btu.
MR24DY3JMA:
FOR (2) ZONES:
Minimum combination must be 50% of
nameplate capacity
FOR (3) ZONES:
Select any combination of (3) indoor
units.
Combinations SHOULD NOT:
Exceed the maximum allowable total
indoor unit connected capacity of
33,000 Btu.
MR48DEY3JM:
FOR (2) ZONES:
Minimum combination must be 50% of
nameplate capacity
FOR (3) ZONES:
Select any combination of (3*) indoor
units per system. *Combination must
be 50% of nameplate capacity.
FOR (4) THROUGH (8) ZONES:
With (3) 18,000 Btu indoor units only a
7,000 or 9,000 Btu indoor can be used.
Combinations SHOULD NOT:
1. Exceed the maximum allowable
total indoor unit connected capacity
of 65,000 Btu.
2. Be below the minimum connectible
capacity of 24,000 Btu.
MR24DY3JMA
33,000 Btu MAX.
CONNECTED
CAPACITY
12,000
18,000
7,000
9,000
12,000
18,000
Ceiling Cassette
Wall-mounted
9,000
12,000
18,000
The Insiderâ„¢
MR36TQY3JMA
48,000 Btu MAX.
CONNECTED
CAPACITY
MR48DEY3JM
65,000 Btu MAX.
CONNECTED
CAPACITY
Mix-and-match a combination of indoor units that does not exceed the
maximum connected capacity, and is within the recommended parameters:
28 | FRIEDRICH J SERIES DUCTLESS