Brochure

PERFORMANCE RATINGS Multizone Wall-Mounted - Heat Pumps
7k 9k 12k 18k
INDOOR MODEL MW07Y3JM MW09Y3J MW12Y3J MW18Y3J
SPECIFICATIONS
CAPACITY COOLING (RATED) Btu 7,000 9,000 11,200 17,000
CAPACITY HEATING (RATED) Btu 8,100 10,800 13,300 20,200
MOISTURE REMOVAL Pts/h NA 2.3 2.7 4.2
AIRFLOW (QUIET, LOW, MED, HIGH) CFM 162/177/198 124/212/272/335 124/212/272/335 300/399/509/622
SOUND RATING - INDOOR dB-A 26/30/33 19 / 24 / 33 / 38 19 / 24 / 33 / 39 29 / 35 / 40 / 45
ELECTRICAL DATA
POWER SOURCE V, Ø, Hz 230/208-60-1 230/208-60-1 230/208-60-1 230/208-60-1
REFRIGERATION SYSTEM
CONNECTIONS Flare Flare Flare Flare
LIQUID LINE O.D. in 1/4 1/4 1/4 1/4
SUCTION LINE O.D. in 3/8 3/8 3/8 1/2
DIMENSIONS & WEIGHT
W X H X D in 34-7/8 x11-1/4 x 8-1/4 35-1/4 x11-1/4 x 8-1/4 35-1/4 x 11-1/4 x 8-1/4 40-5/8 x 12-7/8 x 9-5/8
NET WEIGHT lbs 20 23 23 31
SHIPPING WEIGHT lbs 26 27 27 40
PERFORMANCE RATINGS Multi Outdoor
24k 36k 48k
OUTDOOR MODEL MR24DY3JMA MR36TQY3JMA MR48DEY3JM
SPECIFICATIONS
POWER SOURCE 208/230/60/1 208/230/60/1 208/230/60/1
EST. YEARLY OPERATING COST $ 122~125 170~245 346~400
RUNNING CURRENT COOLING MIN.~RATED~MAX. A 1.7~6.4~9.0 2.9~10.7~15.7 4.6~16.7~24.8
RUNNING CURRENT HEATING MIN.~RATED~MAX. A 1.8~7.8~11.2 3.3~11.9~18.3 6.2~18.8~26.2
POWER INPUT COOLING MIN.~RATED~MAX. W 390~1480~2070 670~2460~3610 970~3840~5710
POWER INPUT HEATING MIN.~RATED~MAX. W 420~1800~2580 760~2740~4210 1420~4320~6020
POWER AND COMMUNICATION CABLE No. x AWG 4 X 14 4 X 14 4 X 14
DIMENSIONS W X H X D inch
34-1/4 x 25-3/4 x12-5/8 37-7/16 x 32-7/8 x 15 1/2 37-3/8 × 54-5/16 × 13
NET WEIGHT lbs 99 137 214
SHIPPING WEIGHT lbs 139 148 236
REFRIGERATION SYSTEM
REFRIGERANT R410A R410A R410A
FACTORY PRECHARGE ft 74 98 Main: 16.4, Branch 131.2
LIQUID LINE O.D. in 1/4 1/4 3/8
SUCTION LINE O.D. in 3/8 3/8 3/4
MIN./MAX. LINE LENGTH (EACH) ft 10~82 10~82 10~49*
MIN./MAX. LINE LENGTH (TOTAL) ft 75~246 75~246 30~476*
MAX. HEIGHT DIFFERENCE ft 49 49 98*
SOUND PRESSURE LEVEL COOLING A 51 52 54
SOUND PRESSURE LEVEL HEATING A 51 55 56
OPERATING RANGE COOLING (WIND BAFFLE) °F DB 14 (-4) ~ 118 14 (-4) ~ 118 14 (-4) -118
OPERATING RANGE HEATING °F WB -4 ~ 64 -4 ~ 64 -4 ~ 64
MINIMUM AMPACITY A 14.3 17.9 27.3
MAX. TD FUSE/BREAKER A 20 25 40
*System requires branch box D4PBB. See page 33 for piping guidelines. For branch box to indoor line sizes, please see Indoor System Components Chart.
Your operating costs will depend on your utility rates and use. The estimated operating cost is based on a electricity cost of $ .12 per kWh.
For more information, visit www.ftc.gov/energy.
Due to continuing research in new energy-saving technology, specications are subject to change without notice.
SPECIFICATIONS