PERFORMANCE RATINGS Single Zone Wall-Mounted - Heat Pumps
9k 12k
SYSTEM MODEL NO. HM09YJA HM12YJA
INDOOR MODEL MWH09Y3JA MWH12Y3JA
OUTDOOR MODEL MRH09Y3JA MRH12Y3JA
SPECIFICATIONS
CAPACITY COOLING (RATED) Btu 9,000 12,000
CAPACITY COOLING (MIN~MAX) Btu 3600-10000 4000-13500
CAPACITY HEATING
@
47
0
F (RATED) Btu 10,715 12,957
CAPACITY HEATING
@
17
0
F (RATED) Btu 6,433 8,030
CAPACITY HEATING (MIN~MAX) Btu 3600-10500 4000-14000
COOLING AMPS 2.3 4.6
HEATING AMPS 3.4 4.8
SENSIBLE HEAT RATIO 0.85 0.85
SEER 28.0 25.0
EER 16.1 15.5
HSPF 12.5 12.0
ENERGY STAR Yes Yes
MOISTURE REMOVAL Pts/h 1.90 2.54
AIRFLOW (QUIET, LOW, MED, HIGH) CFM 416/384/355/279 598/536/446/345
SOUND RATING - INDOOR dB-A 39/34/31/28 45/41/39/36
SOUND RATING - OUTDOOR dB-A 55 55
OPERATING RANGE (COOLING) °F 0˚-115˚ 0˚-115˚
OPERATING RANGE (HEATING) °F -13˚-75˚ -13˚-75˚
EST. YEARLY OPERATING COST $
ELECTRICAL DATA
POWER SOURCE V 208/230/60/1 208/230/60/1
MINIMUM AMPACITY A 10A 12A
COOLING WATTS W 560 775
HEATING WATTS W 770 850
MAX. TD FUSE/BREAKER A 15 15
POWER AND COMMUNICATION CABLE
No. x AWG
4 x 14 4 x 14
REFRIGERATION SYSTEM
REFRIGERANT R410A R410A
COMPRESSOR TYPE Rotary Rotary
CONNECTIONS Flare Flare
LIQUID LINE O.D. in 1/4 1/4
SUCTION LINE O.D. in 3/8 3/8
FACTORY PRECHARGE ft 24.6 24.6
REFRIGERANT CHARGE oz 38.8 45.9
MIN./MAX. LINE LENGTH ft 65.4 65.4
MAX. HEIGHT DIFFERENCE ft 16.4 16.4
DIMENSIONS & WEIGHT
INDOOR UNIT
W X H X D in 32 7/8 x 11 x 8 11/16 36 x 12 3/8 x 9 5/16
NET WEIGHT lbs 19.8 28.6
SHIPPING WEIGHT lbs 24.2 33.0
OUTDOOR UNIT
W X H X D in 31 7/8 x 23 x 11 31 7/8 x 23 x 11
NET WEIGHT lbs 72.6 72.6
SHIPPING WEIGHT lbs 79.2 79.2
TOTAL NET WEIGHT lbs 92.4 101.2
TOTAL SHIPPING WEIGHT lbs 103.4 112.2
Your operating costs will depend on your utility rates and use. The estimated operating cost is based on a electricity cost of $ .12 per kWh.
For more information, visit www.ftc.gov/energy.
Due to continuing research in new energy-saving technology,
specications are subject to change without notice.