Service & Parts Manual (2019, 2020, 2021, 2022)
ManualsBrandsFriedrich ManualsAir ConditionersKuhl Plus Series Smart Heat Pump Window or Wall Air Conditioner with 10000 Cooling BTU, 8800 Heating BTU, 450 sq. ft. Cooling Area, 300 CFM, 4 Cooling Speed, Remote Controller, 115 Volts, 10.9 EER Remote Control, Wi-Fi Enabled, Timer, Auto Restart, Washab
Table Of Contents
58 PB
FAULT
CODE
PROBLEM CONTROL BOARD'S ACTION
1 Front Panel Button Stuck For More
Than 20 Seconds
Continue to monitor for "OPEN" (Unstuck) switch. Do not process
switch input. ENSURE FRONT COVER DOES NOT DEPRESS
BUTTONS
3 Indoor Temperature Sensor is Open
or Shorted
Set temp to 75°F in COOLING or 68°F in HEATING. Unit continues
to operate
4 Indoor Coil Temperature Sensor is
Open or Shorted
Control Board sets temp to a default of 40°F. Override sensor.
Unit continues to operate.
5 Outdoor Coil Temperature Sensor is
Open or Shorted
Sets temp to 20°F. Override sensor. Continue operation. Use Elec
Heat if available for HEATING. If not available use HEAT PUMP if
outdoor temp allows.
6 Outdoor Coil > (greater than) 175 F Shut down for 5 min.
7 Indoor Coil < (less than) 30 F for 2
consecutive minutes
Turn compressor off. When coil temp reachs 45°F resume
operation after lockout time.
8 Unit Cycles > (grater than) 9 Times
per hour
Continue operation. Continue to monitor. Take no action. Log
Only.
9 Unit Cycles < (less than) 3 Times per
Hour
Continue operation. Continue to monitor. Take no action. Log
Only.
12 Discharge Air > (greater than) 185 F Shutdown electric heater until temp is 100°F. Resume
operation.
14 Discharge Air Temperature Sensor
is Open or Shorted
Override Sensor. Set temp to 75°F. Continue to monitor. Set
error code 14 ON.
16 Temperature Beyond Operating
Limits
Ambient temp < (less than) 0°F and ambient temp > (greater
than) 130°F. Set error code 16 ON. When cleared return unit to
normal.
22 Outdoor Coil Temperature < 30 F
for 2 consecutive Minutes
Unit will use electric heat to satisfy heating demands until temp
is greater than 45°F. Unit must be a Heat Pump with electric
heat.
23 Frost Protection. Unit will run active defrost for up to 6 minutes when Heat Pump
run time is greater than 60 minutes and outdoor coil temp is 26 F
or less.
TROUBLESHOOTING
Diagnostic Codes
Figure 710 (Fault Codes)