Installation & Operation Manual (2019, 2020)
44 45
 ♦ Inspect and ensure that all components and accessories have been 
installed properly and that they have not been damaged during the 
installation progress.
 ♦ Check the condensate water drain(s) to ensure that they are 
adequate for the removal of condensate water, and that they meet 
the approval of the end user.
 ♦ Ensure that all installation instructions concerning clearances around 
the unit have been adhered to. Check to ensure that the unit air lter, 
indoor coil, and outdoor coil are free from any obstructions.
 ♦ Ensure that the circuit breaker(s) or fuse(s) and supply circuit wire 
size have been sized correctly. If the unit was supplied with a power 
supply cord, insure that it is stored properly.
 ♦ Ensure that the entire installation is in compliance with all applicable 
national and local codes and ordinances having jurisdiction.
 ♦ Secure components and accessories, such as a decorative front cover.
 ♦ Start the unit and check for proper operation of all components in 
each mode of operation.
 ♦ Instruct the owner or operator of the units operation, and the 
manufacturer’s Routine Maintenance.
NOTE:  A log for recording the dates of maintenance and/ or service is 
recommended.
 ♦ Present the owner or operator of the equipment with the Installation & 
Operation Manual, all accessory installation instructions, and the name, 
address, and telephone number of the Authorized Friedrich Warranty 
Service Company in the area for future reference if necessary.
Heat pumps operate differently
If your unit is a “KH”, or heat pump model, there are some things that you 
will want to be aware of. Some functions of a heat pump differ from your 
unit when it is used for heating:
1.   It is normal for ice to form on the outdoor coil of the heat pump. 
Moisture in the outside air, passing over the coil when very 
cold, will form ice.
2.  If the outdoor temperature drops below 37 °F (3 °C), your heat 
pump will automatically turn on the electric resistance heat. 
When the temperature rises to 40 °F (4 °C), the compressor 
will resume the heat pump operation. If your unit is a 115 volt 
model (KHS10), it is designed for use in warmer climates and 
does not have an electrical heat feature, and will not provide 
adequate heat below 37 °F (2.8 °C).
Control Panel Battery Change Procedure
Remove the grille, by loosening four (4) captive screws (see Figure 84). In 
the upper left corner, remove one (1) screw on the battery retaining door 
(see Figure 85). Remove and replace the battery (CR2450). Reinstall 
the battery retaining door. Align the grille guide pins then tighten the four 
(4) captive screws. Before closing the grille panel door, check the lter. 
Clean or replace it as necessary.
Figure 84
FRR010
USE HAND TOOLS
DO NOT OVERTIGHTEN
Figure 85
Final Inspection & Start-up Checklist
This is a warm weather appliance
Your air conditioner is designed to cool in warm weather when the outside 
temperature is above 60 °F (15.6 °C) and below 115 °F (46.1 °C), so it won’t 
cool a room if it is already cool outside. If you want to cool a room in the 
spring or fall, select the FAN ONLY mode and set the Fresh Air/ Exhaust air 
control to Fresh Air. This will bring in a supply of cooler outside air.
Condensation is normal
Air conditioners actually pump the heat and humidity from your room to the 
outside. Humidity becomes water, and your air conditioner will use most of 
the water to keep the outside coil cool. If there is excessive humidity, there 
may be excess water that will drip outside. This is normal operation.
Frosting
This usually occurs because of insufcient airow across the coils, a dirty 
lter,  cool  damp  weather,  or  all  these.  Set  the  SYSTEM  mode  to  FAN 
ONLY and the frost will disappear. Setting the thermostat a little warmer 
will probably prevent the frosting from recurring.
Noises
All air conditioners make some noise. Friedrich units are designed to 
operate as quietly as possible. An air conditioner mounted in a wall is 
quieter than one mounted in a window. It is important to ensure that the 
chassis seal gasket (Item 13) is properly installed (refer to the Installation 
Instructions).
1.   USE HAND TOOLS WHEN INSTALLING 
AND REMOVING FRONT PANEL.  
DO NOT OVERTIGHTEN SCREWS.
2. DISCONNECT POWER AND FOLLOW 
ALL LABELED WARNINGS WHEN 
FRONT PANEL IS REMOVED.










