Service & Parts Manual (Non Q) (2019, 2020, 2021, 2022)
Table Of Contents
- INTRODUCTION
- SPECIFICATIONS
- OPERATION
- ROUTINE MAINTENANCE
- REMOVE AND INSTALL THE CHASSIS
- R-410A SEALED SYSTEM REPAIR
- COMPONENT TESTING
- Hermetic Components Check
- Reversing Valve Description And Operation
- Testing The Reversing Valve Solenoid Coil
- Checking The Reversing Valve
- Replace The Reversing Valve
- Touch Test Chart : To Service Reversing Valves
- Compressor Checks
- Compressor Replacement
- Fan Motor
- Capacitors
- Heating Element
- Drain Pan Valve
- Testing the User Interface and Electronic Control Board
- Thermistors Description
- Electronic Control Board Identification
- Replace the Electronic Control Board
- Replace the User Interface
- TROUBLESHOOTING
- WIRING DIAGRAMS
- PARTS CATALOG
- Available Accessories
77 PB
HEAT PUMP ROOM AIR CONDITIONERS: TROUBLE SHOOTING TIPS
REFRIGERANT SYSTEM DIAGNOSIS - HEATING CYCLE
LOW SUCTION PRESSURE HIGH SUCTION PRESSURE LOW HEAD PRESSURE HIGH HEAD PRESSURE
Low Airflow Across
Outdoor Coil
Outdoor Ambient Too
High for Operation in
Heating
Refrigerant System
Restriction
Outdoor Ambient Too
High For Operation In
Heating
Refrigerant System
Restriction
Reversing Valve not
Fully Seated
Reversing Valve not
Fully Seated
Low Airflow Across
Indoor Coil
OverchargedUnderchargedOvercharged
Undercharged
Noncondensables (air)
in System
Noncondensables (air)
in System
Defective Compressor
Moisture in System
ELECTRICAL TROUBLESHOOTING CHART - HEAT PUMP
FAULT
SYSTEM COOLS WHEN
HEATING IS DESIRED
Is Selector Switch
Set For Heat?
Is Line Voltage
Present At The
Solenoid?
Is The Solenoid
Good?
YES
YES
Replace The
Solenoid
NO
Is The Reversing
Valve Stuck?
YES
Replace The
Reversing Valve
YES
TROUBLESHOOTING
Figure 718 (Trouble Shooting Tips)