Installation & Operation Manual
6 7
 WARNING
Electrical Shock Hazard
Make sure your electrical receptacle has the 
same conguration as your air conditioner’s 
plug. If different, consult a Licensed Electrician.
Do not use plug adapters.
Do not use an extension cord.
Do not remove ground prong.
Always plug into a grounded 3 prong outlet. 
Failure to follow these instructions can result 
in death, re, or electrical shock.
Make sure the wiring is adequate for your unit.
If you have fuses, they should be of the time delay type. Before you 
install or relocate this unit, be sure that the amperage rating of the 
circuit  breaker  or  time  delay  fuse  does  not  exceed  the  amp  rating 
listed in Table 1.
DO NOT use an extension cord.
The cord provided will carry the proper amount of electrical power to 
the unit; an extension cord may not.
Make sure that the receptacle is compatible with the air 
conditioner cord plug provided.
Proper grounding must be maintained at all times. Two prong receptacles 
must be replaced with a grounded receptacle by a certied electrician.
The grounded receptacle should meet all national and local codes 
and  ordinances.  You  must  use  the  three  prong  plug  furnished with 
the air conditioner. Under no circumstances should you remove the 
ground prong from the plug.
Test the power cord.
All Friedrich room air conditioners are shipped from the factory with 
a Leakage Current Detection Interrupter (LCDI) equipped power 
cord. The LCDI device on the end of the cord meets the UL and NEC 
requirements for cord connected air conditioners.
To test your power supply cord:
1. Plug power supply cord into a grounded 3 prong outlet.
2. Press RESET (see Figure 1).
3. Press TEST, listen for click; the RESET button trips and pops out.
4.  Press and release RESET (Listen for click; RESET button latches and 
remains in). The power cord is ready for use.
WARNING: Before Operating Your Unit
Figure 1
FRR072
WARNING:
TEST BEFORE EACH USE!
1. PRESS REST BUTTON.
2. PLUG LCDI INTO POWER 
RECEPTACLE.
3. PRESS TEST BUTTON, 
RESET BUTTON SHOULD 
POP UP.
4. PRESS RESET BUTTON 
FOR USE.
DO NOT USE IF ABOVE 
TEST FAILS.
WHEN GREEN LIGHT 
IS ON, IT IS WORKING 
PROPERLY!
TEST
RESET
Once plugged in, the unit will operate normally without the need to 
reset the LCDI device. If the LCDI device fails to trip when tested 
or if the power supply cord is damaged, it must be replaced with a 
new power supply cord from the manufacturer. Contact our Technical 
Assistance Line at (800) 541-6645. To expedite service, please have 
your model number available.
Table 1
MODEL
CIRCUIT RATING
OR TIME DELAY
FUSE
REQUIRED
WALL
RECEPTACLE
AMP VOLT
NEMA
NO.
KCS08, KCS10
KCS12, KCS14
KHS10
15 125 5-15R
KCS12, KCS16
KCM18, KCM21
KCL22
15 250 6-15R
KCM24, KCL28
KES12, KES16
KHS12, KCL24
20 250 6-20R
KCL36, KEM18
KEM24, KEL36
KHM18, KHL24
30 250 6-30R
NOTICE
Do not use the LCDI device as an ON/OFF switch.
Failure to adhere to this precaution may cause 
premature equipment malfunction.