TROUBLESHOOTING
Outdoor Fault Codes
Fault code Fault description Possible reasons for
abnormality
How to deal with Remarks
18 AC voltage is abnormal 1.The AC voltage>275V
or <160V. 2.The AC
voltage of sampling
circuit on the driver
board is abnormal.
"1. Normal protection,
please check the supply
power;
2. Replace the driver
board."
19 Suction temperature
sensor fault
"1.The wiring of the
suction tempe- rature
sensor is connected
loosely;
2.The suction
temperature sensor
fails;
3.The sampling circuit is
abnormal."
"1.Reconnect the
wiring of the suction
temperature sensor;
2.Replace the suction
temperature sensor;
3.Replace the outdoor
control board."
22 The defrosting sensor
fault
"1.The wiring of the
defrosting sensor
is connected loosely;
2.The defrosting sensor
fails;
3.The sampling circuit is
abnormal."
"1. Reconnect the wiring
of the defrosting sensor;
2. Replace the
defrosting sensor;
3. Replace the outdoor
control board."
23 Expansion valve A tube
(thin) sensor fault
"1. The wiring of
the sensor for the
expansion valve A(thin
tube) connect loose;
2. The sensor for the
expansion A(thin tube)
is failure;
3. The sampling circuit
is abnormally"
"1. Reconnect the wiring
of the sensor for the
expansion valve A (thin
tube);
2. Replace the sensor
for the expansion valve
A (thin tube);
3. Replace the outdoor
control board."
24 Expansion valve B (thin)
tube sensor fault
"1. The wiring of
the sensor for the
expansion valve B (thin
tube) connect loose;
2.The sensor for the
expansion valve B(thin
tube) is failure;
3.The sampling circuit is
abnormally"
"1. Reconnect the wiring
of the sensor for the
expansion valve B(thin
tube);
2.Replace the sensor
for the expansion valve
B(thin tube);
3. Replace the outdoor
control board."
25 Expansion valve C
(liquid) pipe sensor
fault
"1. The wiring of
the sensor for the
expansion valve
C (liquid pipe) is
connected loosely;
2. The sensor of the
expansion valve C
(liquid pipe) fails;
3. The sampling circuit
fails."
"1. Reconnect the wiring
of the sensor for the
expansion valve C
(liquid pipe).
2. Replace the sensor
for the expansion valve
C (liquid pipe);
3. Replace the outdoor
control board."
26 Expansion valve D
(liquid) pipe sensor
fault
"1.The wiring of
the sensor for the
expansion valve
D (liquid pipe) is
connected loosely;
2.The sensor of the
expansion valve D
(liquid pipe) fails;
3.The sampling circuit
fails."
"1. Reconnect the wiring
of the sensor for the
expansion valve D
(liquid pipe);
2. Replace the sensor
for the expansion valve
D (liquid pipe);
3. Replace the outdoor
control board."