Service and Parts Manual (2019, 2020, 2021, 2022)
Table Of Contents
- _GoBack
- INTRODUCTION
- SPECIFICATIONS
- OPERATION
- R-410A SEALED SYSTEM REPAIR
- COMPONENT TESTING
- TROUBLESHOOTING
- WIRING DIAGRAMS
- PARTS CATALOG
- PARTS CATALOG
- Chill Premier Models: CCW06B10A CCW08B10A CCW10B10A CCW12B10A
- Chill Premier Models: CCW15B10A CCW18B30A
- Chill Premier Models: CCW24B30A
- Chill Premier Models: CEW08B11A, CEW12B33A
- Chill Premier Models: CEW18B33A
- Chill Premier Models: CEW24B33A
- Chill Premier Models: CCF05A10A CCF06A10A CCF08A10A
- Chill Premier Models: CCF10A10A CCF12A10A
- Unifit Models: UCT08A10A UCT10A10A UCT12A10A UCT10A30A
- Unifit Models: UCT12A30A, UCT14A30A
- Unifit Models: UCT10A30B
- Unifit Models: UCT14A30B
- Unifit Models: UET08A11A UET10A33A UET12A33A
- Unifit Models: UET14A33A
- Available Accessories
25 PB
Overcharged Refrigerant Systems
Compressor amps will be near normal or higher.
Noncondensables can also cause these symptoms.
To conrm, remove some of the charge, if conditions
improve, system may be overcharged. If conditions
don’t improve, Noncondensables are indicated.
Whenever an overcharged system is indicated, always
make sure that the problem is not caused by air ow
problems. Improper air ow over the evaporator coil
may indicate some of the same symptoms as an over
charged system.
An overcharge can cause the compressor to fail, since
it would be “slugged” with liquid refrigerant.
The charge for any system is critical. When the
compressor is noisy, suspect an overcharge, when you
are sure that the air quantity over the evaporator coil is
correct. Icing of the evaporator will not be encountered
because the refrigerant will boil later if at all. Gauges
connected to system will usually have higher head
pressure (depending upon amount of over charge).
Suction pressure should be slightly higher.
Figure 602 (Overcharged System)
WARNING
RISK OF ELECTRIC SHOCK
Unplug and/or disconnect all electrical power
to the unit before performing inspections,
maintenances or service.
Failure to do so could result in electric shock,
serious injury or death.
WARNING
HIGH PRESSURE HAZARD
Sealed Refrigeration System contains refrigerant
and oil under high pressure.
Proper safety procedures must be followed,
and proper protective clothing must be worn
when working with refrigerants.
Failure to follow these procedures could
result in serious injury or death.
R-410A SEALED SYSTEM REPAIRS