Service and Parts Manual (2019, 2020, 2021, 2022)
Table Of Contents
- _GoBack
- INTRODUCTION
- SPECIFICATIONS
- OPERATION
- R-410A SEALED SYSTEM REPAIR
- COMPONENT TESTING
- TROUBLESHOOTING
- WIRING DIAGRAMS
- PARTS CATALOG
- PARTS CATALOG
- Chill Premier Models: CCW06B10A CCW08B10A CCW10B10A CCW12B10A
- Chill Premier Models: CCW15B10A CCW18B30A
- Chill Premier Models: CCW24B30A
- Chill Premier Models: CEW08B11A, CEW12B33A
- Chill Premier Models: CEW18B33A
- Chill Premier Models: CEW24B33A
- Chill Premier Models: CCF05A10A CCF06A10A CCF08A10A
- Chill Premier Models: CCF10A10A CCF12A10A
- Unifit Models: UCT08A10A UCT10A10A UCT12A10A UCT10A30A
- Unifit Models: UCT12A30A, UCT14A30A
- Unifit Models: UCT10A30B
- Unifit Models: UCT14A30B
- Unifit Models: UET08A11A UET10A33A UET12A33A
- Unifit Models: UET14A33A
- Available Accessories
24 PB
R-410A SEALED SYSTEM REPAIRS
WARNING
RISK OF ELECTRIC SHOCK
Unplug and/or disconnect all electrical power
to the unit before performing inspections,
maintenances or service.
Failure to do so could result in electric shock,
serious injury or death.
WARNING
HIGH PRESSURE HAZARD
Sealed Refrigeration System contains refrigerant
and oil under high pressure.
Proper safety procedures must be followed,
and proper protective clothing must be worn
when working with refrigerants.
Failure to follow these procedures could
result in serious injury or death.
Undercharged Refrigerant Systems
An undercharged system will result in poor
performance (low pressures, etc.) in both the heating
and cooling cycle.
Whenever you service a unit with an undercharge of
refrigerant, always suspect a leak. The leak must be
repaired before charging the unit.
To check for an undercharged system, turn the unit
on, allow the compressor to run long enough to
establish working pressures in the system (15 to 20
minutes).
During the cooling cycle you can listen carefully at
the exit of the metering device into the evaporator;
an intermittent hissing and gurgling sound indicates
a low refrigerant charge. Intermittent frosting and
thawing of the evaporator is another indication of a
low charge, however, frosting and thawing can also
be caused by insufcient air over the evaporator.
Checks for an undercharged system can be made at
the compressor. If the compressor seems quieter
than normal, it is an indication of a low refrigerant
charge.
A check of the amperage drawn by the compressor
motor should show a lower reading. (Check the
Unit Specication.) After the unit has run 10 to
15 minutes, check the gauge pressures. Gauges
connected to system with an undercharge will have
low head pressures and substantially low suction
pressures.
Figure 601 (Undercharged System)