Service & Parts Manual
Table Of Contents
- _GoBack
- INTRODUCTION
- SPECIFICATIONS
- OPERATION
- R-410A SEALED SYSTEM REPAIR
- COMPONENT TESTING
- Hermetic Components Check
- Reversing valve description and operation
- Testing The Reversing Valve Solenoid Coil
- Checking The Reversing Valve
- Replace The Reversing Valve
- Touch Test Chart : To Service Reversing Valves
- Compressor Checks
- Compressor Replacement
- Compressor Replacement -Special Procedure in Case of Compressor Burnout
- Fan Motor
- Capacitors
- TROUBLESHOOTING
- WIRING DIAGRAMS
- PARTS CATALOG
- Unifit Models: UET14A33A
- Unifit Models: UET08A11A UET10A33A UET12A33A
- Unifit Models: UCT12A30, UCT14A30A
- Unifit Models: UCT08A10A UCT10A10A UCT12A10A UCT10A30A
- Chill Premier Models: CCF10A10A CCF12A10A
- Chill Premier Models: CCF05A10A CCF06A10A CCF08A10A
- Chill Premier Models: CEW24B33A
- Chill Premier Models: CEW18B33A
- Chill Premier Models: CEW08B11A, CEW12B33A
- Chill Premier Models: CEW08B11A, CEW12B33A
- Chill Premier Models: CEW08B11A, CEW12B33A
- Chill Premier Models: CCW24B30A
- Chill Premier Models: CCW24B30A
- Chill Premier Models: CCW15B10A CCW18B30A
- Chill Premier Models: CCW06B10A CCW08B10A CCW10B10A CCW12B10A
- Available Accessories
15 PB
OPERATION
Sequence of Operation
Main function
NOTES:
RT------Room Temperature.
IPT------Indoor Pipe (Coil) Temperature.
ST------indoor Set Temperature.
OPT---Outdoor Pipe (Coil) Temperature.
CRT---Compensated Room Temperature
1. Cooling mode
In the cooling mode, COOL indicator is ON, the set temperature and fan speed could be changed or adjusted.
a. When RT-ST≥ 33.8°F the compressor operates if there is not any protection or failure happened.
b. When RT-ST< 30.2°F the compressor stops, and fan motor keeps operation continuous.
c. When 30.2°F ≤RT-ST<33.8°F the compressor keeps former status.
1.1 Indoor fan motor control
1.1.1 Indoor fan motor could be controlled by Auto, Low, Med and High speed circularly .
1.1.2 Indoor fan motor Auto control as below:
a) In cooling mode T=RT-ST
b) While T<32°F, operates in low speed;
c) If T= 35.6°F, in medium speed
d )If T≥39.2°F , in high speed
e) If 35.6°F < T < 39.2°F , The fan motor runs at original speed while it was set in High or Med mode. If
original at Low speed, it will change to Med speed automatically.
f) If 32°F ≤ T < 35.6°F, , The fan motor operates at original speed while it was set in Low or Med mode. If
original at High speed, it will change to Med automatically.
g) When fan speed changes due to the temperature variation, it could be changed only by sequence as
High, Med to Low speed or Low, Med to High speed, and each status will keep at least 2 minutes.
35.6°
F
39.2°F