Blue-Tube XL Owners Manual
Coil Mount Installation
1. Determine the dimensions of the coils or area to be
irradiated.
2. Use the Coil Sizing Reference to determine the
number of lamps needed for proper coverage.
3. Larger coils may require multiple Tubular Rack Kits
UV Lamp Conguration Guidelines
• Maximum germicidal eectiveness is within an 18” radius
from UV lamp center axis
• The distance between UV lamp(s) and the irradiated
surface should be between 6”-18”, 12” is optimal
• The distance between stacked UV lamps should not
exceed 35”
• The distance between end to end UV lamps should not
exceed 12”
• The distance of UV lamp ends to the edge of irradiated
surface should not exceed 6”
NOTE:
The congurations shown here represent typical UVC
coverage for coil surface disinfection. Adding more
lamps is acceptable and is recommended for airborne
disinfection.
Coil Sizing
Reference
2
32”
32”
SINGLE 32” LAMP
40”
32”
SINGLE 32” LAMP
32”
48”
DUAL 32” LAMPS
40”
48”
DUAL 32” LAMPS
32”
72”
DUAL 32” LAMPS
40”
72”
DUAL 32” LAMPS
32”
18”
SINGLE 32” LAMP