2.2.5. Serial Interface
Serial Interface
Setting Description
Default Setting (0) RS232
Options l (0) RS232 - Also used for TTL.
l (1) RS422/Full Duplex RS485 - Modbus RTU mode must be enabled and
Turn Off Delay set to at least 4.
l (2) Half Duplex RS485 - Modbus RTU mode must be enabled and Turn Off
Delay set to at least 4.
l (3) DOT - DOT causes the CD line to indicate when data is transmitted on the
serial port from the radio.
l When the radio is not sending data to the serial port, CD is de-asserted.
l When the radio is sending data to the serial port, CD is asserted.
l The CD line no longer has any link state functionality.
l Turn Off Delay works as described in all radios.
l Turn On Delay works as described on any Slave or Slave/Repeater - it has
no functionality on the Master.
If set to anything other than 0, the Setup Port parameter in the Baud Rate tab
must be set to Diagnostics Only.
Terminal Menu (1) Set Baud Rate > (C) RS232/485
Description: Use this option to set the protocol of the data port for connection to an external
device.
Note: This setting must be 0 in TTL RF board products.
2.2.6. Setup Port
Important!: Do NOT change this setting unless the correct programming cable is available for the
new setting.
Setup Port
Setting Description
Default Setting (3) Both
The factory setting is based on the radio type.
l A setting of 2 is used with Ethernet products and Mirrored Bit products.
l A setting of 3 is used in other products.