- Choosing a Location for the Transceivers
- Quick Start on a Point-to-Point Network
- Setting up a Transceiver
- Operation Mode
- Baud Rate
- Modbus RTU Timing
- The Modbus RTU setting causes the radio to wait for an amount of time, “gathering” data before sending out the radio link.
- With a setting of 0 (Disabled), the radio will send data out its radio link as soon as the data is received into the serial port.
- With a setting of 1, the radio will wait for a number of slots equal to 2 times the Master Packet Repeat setting before sending the received data out the radio link. For example, if Master Packet Repeat = 3, the radio will wait for 6 slots, gathering ...
- With a setting of 2 and higher, the radio will wait for a number of slots calculated by the following formula:
- (Modbus RTU Setting + Master Packet Repeat Setting + 1) x 2
- For example, in a radio where the Modbus RTU setting = 2 and the Master Packet Repeat setting = 3, the radio will wait for (2+3+1) x 2, or 12 slots.
- Call Book
- Radio Transmission Characteristics
- Edit Radio Transmission Characteristics
- MultiPoint Parameters
- Edit MultiPoint Parameters
- Radio Information
- Operational RS-422 and RS-485 Information
- RS232 Pin Assignments
- RF Board Pinout
- FreeWave Technical Support
- Errata
LRS-455-EU Data Transceiver Users Manual
LUM0032AA Rev A Version 1.0 23
Factory Default Settings
FreeWave 455MHz transceivers are shipped from the factory with the following Default Settings:
Operation Mode
Default
Point to Point Slave
1
Set Baud Rate Default
Baud Rate 19200
(A) Data Parity 0
(B) Modbus RTU 0
(C) RS232/485 0
(D) Setup Port 3
(E) TurnOffDelay/OnDelay 0/0
(F) Flow Control 0
Radio Parameters Default
(1) MAX PACKET SIZE 9
(2) MIN PACKET SIZE 1
(3) XMT RATE 1
(4) RF DATA RATE 5
(5) RF XMT POWER 10
(6) SLAVE SECURITY 0
(7) RTS TO CTS 0
(8) RETRY TIMEOUT 255
(9) LOW POWER MODE 0
(A) High Noise 0
(B) MCU Speed 0
(C) Remote LED 0
MultiPoint Parameters
Default
(1) MASTER PACKET REPEAT 0
(2) MAX SLAVE RETRY 9
(3) RETRY ODDS 0
(4) DTR CONNECT 0
(6) NETWORK ID 255
(7) RESERVED
(8) MULTI MASTER SYNC 0
(9) 1 PPS ENABLE DELAY 255
(B) DIAGNOSTICS 0
(D) RADIO ID Not Set