Installation Owner manual

7 Page 7 - 16 TANK SENTINEL
®
INSTALLATION GUIDE
Figure 7-8c. TS-SEM BriteBox
®
— Connection & Sensor Wiring Details
BRITEBUS (RIBBON CABLE) - TYPICAL
CONNECTION DIAGRAM
J2
BRITEBOX
# 2
J1 J2 J1
BRITEBOX
# 1
J11
OR
J2
BRITEBUS CABLE
RED STRIPE DOWN
(TYPICAL - BOTH ENDS)
J11
CONSOLE
MAIN PCBd
BRITEBUS RIBBON CABLE
DETAIL (RIGHT SIDE LOOPED)
TWO GREEN GROUND WIRES, THROUGH 1/2" (12.7 mm) CONDUIT TO ELECTRICAL PANEL:
EARTH GROUND (NEUTRAL BUSS BAR).
* (POWER) - TO RED COLORED SENSOR WIRES ONLY
(NO CONNECTION IS REQUIRED FOR 2 CONDUCTOR SENSOR CABLES)
* (GROUND) - TO BLACK COLORED SENSOR WIRES ONLY
* (INPUT) - TO WHITE COLORED SENSOR WIRES ONLY
3/4" CONDUIT
FOR
4 SENSORS
HAZARDOUS LOCATION (CLASS I, DIV 1, GROUP D -
NON-HAZARDOUS LOCATION
SENSOR
3/7
PWR (RED)
IN (WHT)
GND (BLK)
GND (BLK)
SENSOR
4/8
Enlarged View
Typical for: J5 & J3
IN (WHT)
PWR (RED)
IN (WHT)
GND (BLK)
IN (WHT)
GND (BLK)
PWR (RED)
PWR (RED)
SENSOR
1/5
SENSOR
2/6
INTRINSICALLY
SAFE WIRING
ONLY)
3/4" CONDUIT
FOR
4 SENSORS
SENS OR 4
SENS OR 5
GND (BL K)
IN (WHT)
PWR (RED )
PWR (RED )
IN (WHT)
GND (BL K)
PWR (RED )
IN (WHT)
GND (BL K)
GND (BL K)
IN (WHT)
SENSOR 1
SENSOR 3
SENSOR 2
EARTH GND
EARTH GND
SENSOR 8
GND (B LK)
PWR (RE D)
IN (WHT)
SENSOR 7
SENSOR 6
GND (B LK)
IN (WHT)
GND (B LK)
IN (WHT)
PWR (RE D)
PWR (RE D)
GND (B LK)
IN (WHT)
PWR (RED )
J2
D1
J4
J5
J3
PWR (RE D)
F1
J1
EARTH GND
EARTH GND
J4
Enlarged
TS-SEM BriteBox #1
(OPTIONAL:
Sensor Expansion Module)
NOTE:
1) SEE N.E.C. / C.E.C. FOR INTRINSICALLY SAFE WIRING.
2) TYPICAL LEAK DETECTION SENSOR WIRING CONNECTIONS
ARE SHOWN.
3) SEE SENSOR INSTALLATION INSTRUCTION MANUAL(S)
FOR ADDITIONAL DETAILS.
4) * = MAX. CABLE LENGTH BETWEEN THE TS-SEM AND
ANY LEAK DETECTION SENSOR MUST NOT EXCEED 1500 FEET.
5) EACH GND TERMINAL MUST BE CONNECTED TO A
SUITABLE SYSTEM EARTH GROUND. DC RESISTANCE BETWEEN
GND TERMINALS AND EARTH GROUND MUST BE LESS THAN 1 OHM.
6) REMOVE THE JUMPER LINK BEFORE WIRING A SENSOR.
ONLY UNUSED SENSOR CHANNELS MUST HAVE THE
JUMPER WIRE INSTALLED BETWEEN THE IN & GND
TERMINALS.
J8
U47
J9
J11
RIBBON CABLE
(INSTALLED WITH
RED STRIPE
DOWN -
TYPICAL
BOTH ENDS)
J7
U36
D12
TX D
S1
D13
D14
RXD
DTR
D15
DCD
J5
U35
J10
J4
J3
J6
J32
U45
TP3
J12
MAIN
SYSTEM
PC Bd
170- 1054
D2
U10
TS-2001/N-N U10
VER No. DATE
J22
J2
J1
TP2
TP1
J33