Installation Owner manual

7 Page 7 - 6 TANK SENTINEL
®
INSTALLATION GUIDE
TABLE 7-2 230 VAC Line Power Wire Connection List:
Electrical Panel No. Conductors, Color (Gauge) Circuit Console Terminal
10 Amp C.B. (Load) 1 Black wire,16 AWG (1.3 mm) min. 230 VAC Power
**
J17 - L1
Ground Bus 1 White wire,16 AWG (1.3 mm) min. Neutral J17 - L2 (NEUT)
Ground Bus 1 Green wire,16 AWG (1.3 mm) min. Ground J17 - GND
Ground Bus 1
*
Green wire,12 AWG (2.1 mm) min. Safety Ground J17 - SAFETY GND
*
= two (2) Safety Ground wires may be required in some locations (check your Local and
National Electric Codes).
** = This is Euro-standard 230 VAC power configuration – L2 is Neutral. The Model/SN
label will indicate 230 VAC.
NOTE
NOTE
Figure 7-3b. 230 VAC Power and I.S. Ground Wiring
ELECTRICAL POWER PANEL
(SHOWN WITH COVER REMOVED)
OFF OFF
MAIN
20
OFF
3 4
OFF
15
20
OFF
1 2
OFF
10
- CIRCUIT ASSIGNMENT LABEL -
ELECTRICAL POWER PANEL DOOR
BACK SIDE VIEW
A
LIG HTS 10A
COOLER 15A
11
12
TANK 10A
SENTIN EL
15 16
13
14
PUM P#1 20A
7 8
9
10
5 6
1
2
3
4
B
N
REDUNDANT
INTRINSIC SAFETY
GROUND
GREEN WIRE, 12 AWG
(2.1 mm) MIN.
- REQUIRED IN
SOME AREAS -
NOTE:
SOME CONSOLES
MAY HAVE TEXT
DESIGNATIONS THAT
DIFFER SLIGHTLY
FROM WHAT
IS SHOWN HERE.
CU EARTH
GROUND ROD
SAFETY
GND
INTRINSIC SAFETY GROUND
(GREEN WIRE, 12 AWG (2.1 mm) MIN.)
NEUTRAL
BUS
GREEN (GND-GROUND) WIRE, 16 GA. (1.3 mm) MIN.
WHITE (L2-NEUTRAL) WIRE, 16 GA. (1.3 mm) MIN.
TANK SENTINEL
CONSOLE
POW ER
GND
L1
NEUT
BLACK (L1-LINE) WIRE, 16 GA. (1.3 mm) MIN.
16
15
10
OFF
GROUND
BUS
Enclosure
Nut
Lock Washer
Earth Ground Conductor
Cup Washer
Stud: #8 threaded post
The installer is to connect the Earth Ground
Conductor to the most convenient ground
terminal as long as it meets local and national
codes. If the ground stud is to be used the
installer shall follow the proper stacking
configuration shown in figure 7-3c The earth
ground conductor must be 12 AWG (2.1 mm)
or larger.
NOTE
Figure 7-3c. Ground Stud