User Manual
TroubleShooting & Maintenance Page 5 - 7
5
TABLE 5 - 1 (CONTINUED... )
ALARMS & ERROR MESSAGES
NOTE:
Diagnostic text
in the left column, is shown
bolded
{ become alarms if active for 48 hours }
#
Printed / Faxed / Displayed
Alarm / Warning Text:
Alarm Type:
System WARNING / Error Descriptions and
ALARM Descriptions
(actions to take)
68
WATCHDOG TIMEOUT / WD
TIMEOUT
SYSTEM
WARNING - the console self-monitoring program
has detected a software or power quality problem
(this error may happen after hardware upgrades)
69
WATER VOLUME ERROR /
WTR VOL ER / WTR VOL
SYSTEM
WARNING - Water Volume calculation error
(Error in tank shape / probe type or special probe
data - OR - no water float / level signal from probe.
Call service provider to correct this.)
70
HIGH HIGH / HIGH HIGH
LIMIT
TANK
High High product level Limit @ Tank N
(see
procedures at your site about this alarm / overfill)
71
HIGH LIMIT TANK
High product level Limit @ Tank N
(see
procedures at your site about this alarm / overfill)
72
LARGE THEFT TANK
Generated by TS-DIM unit. The amount of product
dispensed exceeded the programmed User
Threashold value, and/or exceeded the number of
Dispensers in use. Also caused by a Catastrophic
Leak. (see policy procedures at your site)
73
LOW LIMIT TANK
Low product level Limit @ Tank N
(see policy
procedures at your site)
74
LOW LOW LIMIT / LOW LOW TANK
Low Low product level Limit @ Tank N
(see policy
procedures at your site)
75
OVERFILL TANK
The overfill limit has been reached or exceeded.
Stop filling tank / Lower the product level.(see
policy procedures at your site)
76
WATER LIMIT (or HIGH
WATER)
TANK
The high Water level Limit has been reached or
exceeded @ Tank N
(see procedures at your site
about this alarm, is a Grace Period allowed ? how
many ?)