TroubleShooting & Maintenance Page 5 - 5
5
TABLE 5 - 1 (CONTINUED... )
ALARMS & ERROR MESSAGES
Keep accurate and dated records, or printouts, of all alarms when they happen and
when they clear.
Contact your Tank Sentinel service provider if the same alarms occur
often or repeatedly... multiple alarms are not normal.
NOTE
NOTE:
Diagnostic text
in the left column, is shown
bolded
{ become alarms if active for 48 hours }
#
Printed / Faxed / Displayed
Alarm / Warning Text:
Alarm Type:
System WARNING / Error Descriptions and
ALARM Descriptions
(actions to take)
44
FAX SND FAIL / FAX SND SYSTEM
WARNING - Fax Send Failure...
(check Dial tone,
cable, call service provider... are the fax phone
numbers correct ?)
45
FLOAT HEIGHT / FLOAT HT /
FLT HT
SYSTEM
WARNING - Float Height - calculation Error
(setup
program error... call service provider)
46
FLOAT MISSING / FLT
MISSNG /
FLT MIS
SYSTEM
WARNING - diagnostic warning Float Missing
(call
service provider)
47
LEAK SYSTEM
WARNING - a Leak detected @ Tank N during the
after hours Sentinel mode
(shut down dispensing,
see procedures at your site... 1. Shut off pump /
dispenser power 2. Retest / start a Standard 0.2
gph tank test for Tank N, 2 hours after the last
dispense
3. Retest & See Chapters 3 & 4
LEAK (Continued )SYSTEM
3. Second confirming failure: Call Service
provider / local Regulatory Agency / Manager per
policy procedure at your site or 4. Second Test
passes [false leak failure]... turn pump and
dispenser power back on and restore normal
operation.
48
LEVEL ERROR / LEVEL ERR
/ LVL ERR
SYSTEM
WARNING - product Level - calculation Error
(call
service provider to fix this problem)
49
MEMORY ERROR / MEM
ERR
SYSTEM
WARNING - Memory Error (power quality problem,
or memory-backup battery is dead...
have service
provider check / replace battery and verify that
unit works correctly as originally programmed)
50
NO PROBE /
NO PROB
SYSTEM
diagnostic WARNING - No Probe Detected
NO
PROB
(call service provider to correct this
problem)
51
PAPER OUT SYSTEM
The printer is out of paper
(add new roll of TS-TP2
thermal paper)
52
POWER DOWN SYSTEM
WARNING - Power Down (time that
the unit lost
power or was turned off
)
53
POWER UP SYSTEM
WARNING - Power Up (time that the unit was
powered up / regained power)
54
PROBE SYNC /
PRB SYC
SYSTEM
Diagnostic WARNING - signal lost from Probe
(
PRB SYC
call service provider if continuous)