User Manual
3
Page 3 - 30 Tank Sentinel Operator’s Guide
Sample Reports (CONTINUED... )
Generator Run REPORT
This report shows when the generator started (BEGIN)
and stopped (
END) and the fuel consumed (USAGE &
USAGE RATE
) during the run.
This report is available only with consoles that have the
special Emergency Generator application software.
Press:
Press: Report Choices
+
2 x
Print Test REPORT
This report (at left without the standard header) checks
the operation and function of the printer. The printing
should be uniformly dark, clear, and legible.
Press: and
Generator Run Report:
Gen Run M1
Choose Printer
or Fax
Press the
DOWN
ke
y
to show this report.
Displa
y
ed with Emer
g
enc
y
Generator
Applications onl
y
.
M1
JW
REPORT
9
KX
DOWN
SPACE
MZ
CHECK
.
M2
RIGHT
INCON
INTELLIGENT CONTROLS INC.
P.O. BOX 638
SACO ME 04072
1-800-984-6266
6/17/2002 2:15 PM
GENERATOR RUN REPORT
INPUT
AUXILIARY 1
TANK 1 3918.47
GAL
PROD 1 #2 FULE OIL
BEGIN TIME 10:45 AM
BEGIN DATE 06/17/2002
BEGIN GROSS 3136.2 GAL
BEGIN NET 3129.4 GAL
BEGIN LEVEL 26.775 IN
BEGIN WATER 1.120 IN
BEGIN WATER 24.5 GAL
BEGIN TEMP 68.459 F
END TIME 11:58 AM
END DATE 06/17/2002
END GROSS 3118.3 GAL
END NET 3118.5 GAL
END LEVEL 24.875 IN
END WATER 1.120 IN
END WATER 24.5 GAL
END TEMP 68.559 F
GROSS USAGE 17.9 GAL
NET USAGE 15.0 GAL
USAGE RATE 13.250 GPH