Page 3 - 28 Tank Sentinel Operators Guide
Sample Reports (CONTINUED... )
CPM Alarm Report
The CPM alarm report (at right) is generated when the current
level is below the setpoint, which is programmed. A CPM
failure will be produced if communication is lost between the
tank gauge and the TS-CPM unit (this may also be a result
to the TS-CPM loosing power). Alarm report(s) will only be
produced when SETUP> SYSTEM> REP ALARM> (report
alarms) is ENABLED.
Press: Press:
Report Choices
+
CPM Status Report
The CPM Status Report is available on demand for printing
at the tank gauge printer, or for faxing. A normal CPM Status
Report is shown at right. This time-stamped report shows the
voltage, current, and operational status for the unit, it would
show ALARM for the STATUS when in alarm.
It can be produced by:
Pressing the REPORT key>
DOWN key 2 or 3 times>
Pushing the menu key (
M1
through
M4
) that is directly
below the
CPM
text>
Pushing
M1
below the displayed
PRINTER
text, or by
pushing
M2
below the displayed
FAX
text.
CPM Status Report:
Alarm Status M1
Choose Printer
or Fax
M1
JW
REPORT
9
KX
DOWN
SPACE
INCON
INTELLIGENT CONTROLS INC.
P.O. BOX 638
SACO ME 04072
1-800-984-6266
ALARM REPORT
2/1/2002 05:55 AM
CPM CURRENT LOW
2/1/2002 08:35 PM
CPM FAILURE
INCON
INTELLIGENT CONTROLS INC.
P.O. BOX 638
SACO ME 04072
1-800-984-6266
ALARM REPORT
1/10/2002 08:02 AM
CATHODIC PROTECTION
VOLTAGE 15.0 V
CURRENT 10.0 A
STATUS OK