Operators Guide User guide

29
FMS
Tank/Manifold Alarms
Displayed Alarm Description Recommended Actions Reference Source
Correction Table
Error
Correction points for the special 
tank listed with the alarm were not 
entered or were entered incorrectly.
Verify that the correction table points for the tank 
listed with the alarm are entered sequentially in 
‘Special Tanks’ Programming.
Special Tanks Setup in 
Programming Manual 
/ Manufacturers’ Tank 
Chart*
Manifold Gross
Leak Detected
The manifold listed with the alarm 
has failed a Gross Leak Test. 
Review manifold leak test history and 
programming. It may be necessary to manually 
start a Gross Leak Test to keep the manifold in 
compliance.
Tank Leak Tests -    
Type and Frequency
Manifold Leak
Detected
The manifold listed with the alarm 
has failed a Monthly Leak Test. 
Review manifold leak test history and 
programming. It may be necessary to manually 
start a Monthly Leak Test to keep the manifold 
in compliance.
Tank Leak Tests -    
Type and Frequency
Manifold SCALD
Leak Detected
The manifold listed with the alarm 
has failed a SCALD Leak Test. 
Review manifold leak test history and 
programming. It may be necessary to manually 
start a SCALD Leak Test to keep the manifold in 
compliance.
Tank Leak Tests -    
Type and Frequency
Manifold Theft
Detected
Product level in the manifold listed 
with the alarm has dropped below 
the programmed Theft Limit.
Verify that the programmed Theft limit is correct. 
Verify that the values of product loss on the 
console correspond with actual product loss in 
the tank.
Manifolds Setup in
Programming Manual
No Data Available SCALD software has not observed 
enough ‘quiet time’ to complete one 
or more test intervals.
Allow enough time for SCALD to complete a 
test.
Tank Leak Tests -    
Type and Frequency
Tank Gross Leak
Detected
The manifold listed with the alarm 
has failed a Gross Leak Test. 
Review manifold leak test history and 
programming. It may be necessary to manually 
start a Gross Leak Test to keep the tank in 
compliance.
Tank Leak Tests -    
Type and Frequency
Tank Leak
Detected
The tank listed with the alarm has 
failed a Monthly Leak Test. 
Review tank leak test history and programming. 
It may be necessary to manually start a Monthly 
Leak Test to keep the tank in compliance.
Tank Leak Tests -    
Type and Frequency
Tank SCALD Leak
Detected
The tank listed with the alarm has 
failed a SCALD Leak Test. 
Review tank leak test history and programming.  Tank Leak Tests -    
Type and Frequency
Tank Theft
Detected
Product level in the tank listed with 
the alarm has dropped below the 
programmed Theft Limit.
Verify that the programmed Theft Limit is 
correct. Verify that the values of product loss on 
the console correspond with actual product loss 
in the tank.
Tanks Setup in
Programming Manual
* Bulletins and the T5 Series Installation Guide (p/n 000-2150) and the T5 Series Programming Manual (000-2142) can be found on 
Franklin Fueling’s web site - http://www.franklinfueling.com/service/.   Select Technical Documentation / Fuel Management System
*  If the tank is not listed as a standard tank in Appendix A: Standard Tanks Table (in the T5 Series Programming Manual (p/n 000-
2142), use the tank chart from the manufacturer to create a custom correction table.