Operators Guide Manual

33
FMS
Special Product Alarms
Displayed Alarm Description Recommended Actions Reference Source
Alpha Volume
Correction Error
These Alarms refer to temperature 
correction coefcients used by the 
console to calculate Net Volume. When 
these values are entered too high or 
too low, an alarm condition will occur.
Verify that the Volume in the Correction 
Type matches the specications of 
the product used in ‘Special Products’
Programming. These values should be 
listed in the product manufacturer’s Spec 
Sheets.
Special Products in
Programming Manual** 
/ Applicable Product 
Literature***
API Volume
Correction Error
These Alarms refer to temperature 
correction coefcients used by the 
console to calculate Net Volume. When 
these values are entered too high or 
too low, an alarm condition will occur.
Verify that the Volume in the Correction 
Type matches the specications of 
the product used in ‘Special Products’
Programming. These values should be 
listed in the product manufacturer’s Spec 
Sheets.
Special Products in
Programming Manual** 
/ Applicable Product 
Literature***
Level Error The level of the product oat on 
the probe listed with the alarm has 
exceeded a possible level according to 
the programming.
Verify that the following parameters are 
programmed correctly according to site 
specications: Correction Table, Gradient, 
Probe Type, and Product Offset.
Probes Setup in
Programming Manual** 
/ Applicable Equipment 
Guide*
Net Error The net volume of the product oat 
on the probe listed with the alarm has 
exceeded a possible volume according 
to the programming; related to Volume 
Correction.
Verify that the following parameters are 
programmed correctly according to site 
specications: Correction Table, Gradient, 
Probe Type, and Product Offset.
Special Products in
Programming Manual** 
/ Applicable Product 
Literature***
Product Volume
Error
The volume of the product oat on 
the probe listed with the alarm has 
exceeded a possible volume according 
to the programming.
Verify that the following parameters are 
programmed correctly according to site 
specications: Correction Table, Gradient, 
Probe Type, and Product Offset.
Probes Setup in
Programming Manual** 
/ Applicable Equipment 
Guide*
Ullage Error The Ullage level on the tank/manifold 
listed with the alarm has exceeded 
a possible level according to the 
programming.
Verify that the following parameters are 
programmed correctly according to site 
specications: Correction Table, Gradient, 
Probe Type, and Product Offset.
Special Products in
Programming Manual** 
/ Applicable Product 
Literature***
Water Volume
Error
The Water Volume on the tank/
manifold listed with the alarm has 
exceeded a possible level according to 
the programming.
Verify that the following parameters are 
programmed correctly according to site 
specications: Correction Table, Gradient, 
Probe Type, and Product Offset.
Special Products in
Programming Manual**/ 
Applicable Product 
Literature***
* Bulletins and Equipment Guides can be found on INCON’s web site - http://www.incon.com
** The T5 Series Installation Guide (p/n 000-2150) and the T5 Series Programming Manual (000-2142) can be found on INCON’s 
web site - http://www.incon.com 
*** If the tank is not listed as a standard tank in Appendix A: Standard Tanks Table (in the T5 Series Programming Manual (p/n 000-
2142), use the tank chart from the manufacturer to create a custom correction table.