Operators Guide Manual
33
FMS
Special Product Alarms
Displayed Alarm Description Recommended Actions Reference Source
Alpha Volume
Correction Error
These Alarms refer to temperature
correction coefcients used by the
console to calculate Net Volume. When
these values are entered too high or
too low, an alarm condition will occur.
Verify that the Volume in the Correction
Type matches the specications of
the product used in ‘Special Products’
Programming. These values should be
listed in the product manufacturer’s Spec
Sheets.
Special Products in
Programming Manual**
/ Applicable Product
Literature***
API Volume
Correction Error
These Alarms refer to temperature
correction coefcients used by the
console to calculate Net Volume. When
these values are entered too high or
too low, an alarm condition will occur.
Verify that the Volume in the Correction
Type matches the specications of
the product used in ‘Special Products’
Programming. These values should be
listed in the product manufacturer’s Spec
Sheets.
Special Products in
Programming Manual**
/ Applicable Product
Literature***
Level Error The level of the product oat on
the probe listed with the alarm has
exceeded a possible level according to
the programming.
Verify that the following parameters are
programmed correctly according to site
specications: Correction Table, Gradient,
Probe Type, and Product Offset.
Probes Setup in
Programming Manual**
/ Applicable Equipment
Guide*
Net Error The net volume of the product oat
on the probe listed with the alarm has
exceeded a possible volume according
to the programming; related to Volume
Correction.
Verify that the following parameters are
programmed correctly according to site
specications: Correction Table, Gradient,
Probe Type, and Product Offset.
Special Products in
Programming Manual**
/ Applicable Product
Literature***
Product Volume
Error
The volume of the product oat on
the probe listed with the alarm has
exceeded a possible volume according
to the programming.
Verify that the following parameters are
programmed correctly according to site
specications: Correction Table, Gradient,
Probe Type, and Product Offset.
Probes Setup in
Programming Manual**
/ Applicable Equipment
Guide*
Ullage Error The Ullage level on the tank/manifold
listed with the alarm has exceeded
a possible level according to the
programming.
Verify that the following parameters are
programmed correctly according to site
specications: Correction Table, Gradient,
Probe Type, and Product Offset.
Special Products in
Programming Manual**
/ Applicable Product
Literature***
Water Volume
Error
The Water Volume on the tank/
manifold listed with the alarm has
exceeded a possible level according to
the programming.
Verify that the following parameters are
programmed correctly according to site
specications: Correction Table, Gradient,
Probe Type, and Product Offset.
Special Products in
Programming Manual**/
Applicable Product
Literature***
* Bulletins and Equipment Guides can be found on INCON’s web site - http://www.incon.com
** The T5 Series Installation Guide (p/n 000-2150) and the T5 Series Programming Manual (000-2142) can be found on INCON’s
web site - http://www.incon.com
*** If the tank is not listed as a standard tank in Appendix A: Standard Tanks Table (in the T5 Series Programming Manual (p/n 000-
2142), use the tank chart from the manufacturer to create a custom correction table.