Operators Guide Manual

32
FMS
Line/Manifold Alarms
Displayed Alarm Description Recommended Actions Reference Source
Dispenser Test
Failed
Line pressure must be above 12 psi 
when the pump is on; and above 7.5 psi 
while dispensing product.
Details of this test are summarized in LS500
Installation/User Guide (p/n 000-2145); see 
this guide for troubleshooting.
Applicable Equipment 
Guide*
Extended Hook
Signal
A hook signal has been active for more 
than four hours.
Details of this test are summarized in LS500
Installation/User Guide (p/n 000-2145); see 
this guide for troubleshooting.
Applicable Equipment 
Guide*
Failed to Catch
Pressure
Line pressure has dropped below 12 psi 
when the pump turned off.
Details of this test are summarized in LS500
Installation/User Guide (p/n 000-2145); see 
this guide for troubleshooting.
Applicable Equipment 
Guide*
Failed to
Pressure Up
Line pressure remained below 12 psi 
when the pump turned on.
Details of this test are summarized in LS500
Installation/User Guide (p/n 000-2145); see 
this guide for troubleshooting.
Applicable Equipment 
Guide*
Gross Leak
Detected
The product line listed with the alarm 
has failed a Gross Leak Test. 
Details of this test are summarized in LS500
Installation/User Guide (p/n 000-2145); see 
this guide for troubleshooting.
Applicable Equipment 
Guide*
Monthly Leak
Test Failed
The product line listed with the alarm 
has failed a Monthly Leak Test. 
Details of this test are summarized in LS500
Installation/User Guide (p/n 000-2145); see 
this guide for troubleshooting.
Applicable Equipment 
Guide*
Annual Leak Test
Failed
The product line listed with the alarm 
has failed a Precision Leak Test. 
Details of this test are summarized in LS500
Installation/User Guide (p/n 000-2145); see 
this guide for troubleshooting.
Applicable Equipment 
Guide*
High Pump
Pressure
Line pressure has exceeded 50 psi.  Details of this test are summarized in LS500
Installation/User Guide (p/n 000-2145); see 
this guide for troubleshooting.
Applicable Equipment 
Guide*
Line is Not
Congured
The line listed with the alarm is not 
congured in ‘Lines’ programming, or 
the line is not properly mapped.
Programming details are summarized in 
LS500 Installation/User Guide (p/n 000-
2145); see this guide for troubleshooting.
Lines Setup in
Programming Manual** 
/ Applicable Equipment 
Guide*
Line Disabled The input channel for the 4-20mA
module connected to the line listed with 
the alarm is not congured.
Verify programming of the 4-20mA Module 
connected to the line listed with the alarm.
Module Setup in
Programming Manual** 
/ Applicable Equipment 
Guide*
Not Enabled The product line listed with the alarm is 
not enabled in the programming.
Programming details are summarized in 
LS500 Installation/User Guide (p/n 000-
2145); see this guide for troubleshooting.
Applicable Equipment 
Guide*
Not Learned The product line listed with the alarm 
has not been learned.
Programming details are summarized in 
LS500 Installation/User Guide (p/n 000-
2145); see this guide for troubleshooting.
Applicable Equipment 
Guide*
Pressure
Transducer
Failed
This alarm indicates a communication 
error between the console and the 
pressure transducer listed with the 
alarm.
Verify the wiring and operation of the 
transducer connected to the line listed with 
the alarm.
Applicable Equipment 
Guide*
Program Error
Detected
Firmware failed to function properly. Upload the current rmware release. Applicable Bulletins*
Pump Request
Ignored
The signal sent by the 4-20mA channel 
did not receive conrmation to turn on 
the pump listed with the alarm.
Verify 4-20mA and Relay Module 
programming.
Module Setup in
Programming Manual** 
/ Applicable Equipment 
Guide*
Sudden Pressure
Loss
Line pressure has dropped from 
above 12 psi to below 5 psi within ve 
seconds.
Details of this test are summarized in LS500
Installation/User Guide (p/n 000-2145); see 
this guide for troubleshooting.
Applicable Equipment 
Guide*
* Bulletins and Equipment Guides can be found on INCON’s website - http://www.incon.com
** The T5 Series Installation Guide (p/n 000-2150) and the T5 Series Programming Manual (000-2142) can be found on INCON’s 
website - http://www.incon.com