Installation Guide User guide

8
Splice Connector Kits Must Be Used — Warranty Requirement
Use the INCON-approved, moisture-resistant, no-strip splice connectors for liquid level probe and leak detection sensor 
wires. You may order the TSP-KW30, which contains 30 of the INCON-approved, moisture-resistant connectors.
Using moisture resistant splice connectors will:
 • Reduce/eliminate corrosion of the wire connections from repeated exposure to water condensation, which causes 
eventual signal loss and system failure.
 • Reduce/eliminate equipment damage from water ooding around the connectors, which causes short-circuit damage.
Thread Sealant (UL Classied)
Use a non-hardening, “stay-soft,” thread sealant approved for gasoline applications to seal and waterproof all tank 
riser pipe threads. In addition, the thread sealant (or “pipe dope” as it is commonly known) should also be chemically 
non-reactive to the product in the tank(s). Apply thread sealant to seal/waterproof all outdoor electrical conduit tting 
threads including the hole plugs at the weatherproof junction boxes.
Riser Pipes
ANSI Schedule 40  (or chemically non-reactive) – 4 inch (101.6 mm) (8 NPT) riser pipes for liquid level probes. See the 
appropriate leak detection sensor installation manual for information on required riser pipes and riser cap adapters.
Probe Installation Kit(s)
See the TSP-LL2’s installation instructions that came with the probe for the items included with the TSP-K4A standard 
probe installation kit. For chemical applications, see the TSP-LL2C’s installation instructions for the TSP -K4AS stainless 
steel riser cap adapter kit and the TSP-SSP stainless steel product oat.
TSP-LL2 Probe Floats
 • Floats for 4 inch (101.6 mm) riser pipes, order: TSP-IGF4 for gasoline applications or TSP-IDF4 for diesel and fuel oil
 • Floats for 3 inch (76.2 mm) riser pipes, order: TSP-IGF3 for gasoline applications or TSP-IDF3 for diesel and fuel oil
 • Floats for 2 inch (50.8 mm) riser pipes, order: TSP-IGF2 for gasoline, TSP-IDF2 for diesel and fuel oils, or TSP-SSP 
stainless steel oat for chemical products
Manufacturers Tank Chart for Each Tank
The manufacturer’s Tank Chart and other documentation will be used for installation and programming, and possibly for 
future reference. Keep this information — do not discard it.