This manual contains installation instructions for the  
INCON S940 Alarm Console. 
Please carefully read this entire manual. Failure to 
follow the instructions in this manual may result in faulty 
operation, equipment damage, injury or death. 
This equipment should only be serviced by an INCON-
certied technician.
Product Description
The 4-channel Alarm console is a stand-alone unit that 
monitors 4 intrinsically safe sensor contact closures and 
provides a visual and audible alarm should one of the 
normally closed contacts become open.
The unit also provides 2 SPDT dry relay contacts that can 
be set to activate upon an alarm condition. 
The S940 is typically used to monitor sumps, overll or 
spill-containment areas.
Specications
Console Specications
Input Line Voltage: 100-240  VAC + / - 10%, 50 / 60 Hz, 15W max
Input power fuse 
rating 
1A, 250 VAC, time delay
Operating 
temperature
-25º C (-13º F) to +60º C (+140º F)
Enclosure NEMA 4, indoor / outdoor *
(Non-hazardous locations only)
Dimensions 6" X 6" x 4" (15.2 cm x 15.2 cm x 10.2 cm)
Relay contact rating 10A, 240VAC maximum (non-fused)
Conduits Two NPT, ½"
Intrinsic safety Class I, Div 1, Group D
* For outdoor use application, listed Type 4X conduit hubs 
must be used.
Note:  For power supply connection, use wires rated at 
least 90 ºC (194 ºF).
Installation
Mounting
To mount the unit to the wall, rst attach the included 
mounting tabs to the box (gure 1) and then attach it to 
the wall.
Figure 1: Box Mounting Tab
Power Supply Wiring
NOTE: The S940 Alarm Console is set to operate with 
between 100 to 240 VAC, 50 / 60 Hz. No setup is required.
The Alarm Console must be connected to a dedicated 
circuit breaker, at the service panel, not exceeding 15 
Amps.
To access wiring and programming, remove the 4 corner 
phillips-head screws on the faceplate and pull the 
faceplate straight out by holding the two faceplate knobs.
Electrical Hazard! Disconnect main
power to the console before removing
the faceplate.
INTRINSICALLY
Rigid Conduit
Shown with wiring
shield cover removed
110/220 VAC
AC power
INTRINSICALLY SAFE WIRING ONLY
SAFE AREA
Relay
Connections
Figure 2: Installation Wiring