Installation Guide

3
Step 2: Match the inverter with wall bracket
Hang the inverter over the bracket, slightly lower the inverter, and make
sure the two mounting grooves on the back are properly fixed with the
two bracket bars.
Model (kW)
0.7
1.0
1.5
2.0
2.5
3.0
3.3*
Cable
2.5mm²
2.5mm²
2.5mm²
4mm²
4mm²
4mm²
4mm²
Micro-Breaker
16A
16A
16A
25A
25A
25A
25A
AC Wiring
-
Cable dimensions
Wiring Steps
Insert the expansion tubes into the holes
and tighten them. Install the bracket
with the expansion screws.